D9412GV2/D7412GV2 | Operation and Installation Guide | 8.0   On-Board Points 
 
32 
Bosch Security Systems, Inc. | 5/05 | F01U003641B 
 
8.4 
Point Response Time 
The control panel scans both on-board and off-board 
point sensor loops every 300 ms. The Debounce 
program item in the Point Assignment section of the 
software determines point response time by setting the 
number of times the control panel scans a point before 
generating an alarm. 
The debounce count can range from 2 to 15; therefore, 
point response time ranges from 600 ms to 4.5 sec. The 
Bosch Security Systems default for debounce count is 2. 
 
Increasing debounce might cause missed 
alarms. If you increase the debounce count, 
detection devices can enter alarm and reset 
without exceeding the point response time. 
Use a debounce count of 2 for all points except for 
Interior Follower points. Program Interior Follower 
points as 3. Program door points connected to a 
D9210B Access Control Interface Module with a 
debounce of 4. 
8.5 
Wiring Information for Installations 
Using the Ademco AB-12 
Bell/Housing 
1.  Disconnect the wire jumper from Terminal 4 to the 
inner housing of the Bell Box to prevent a ground 
fault condition. 
2.  Connect wiring between the control and Bell Box 
(Figure 11 on page 33).  
 
To use the AB-12 Bell/Housing, place the S3 
switch in the disabled (open) position. The EOL 
used in the AB-12 Bell/Housing must be a 220 k
Ω
0.5 W resistor. 
3.  Program Point 8 as 24-hour, alarm on, open, and 
short. (PT TYPE 0, PT RESPONSE 0).