Frequency setting by external terminals
4
4.11.2 Jog operation (Pr. 15, Pr. 16)
The above parameters are displayed as simple mode parameters only when the parameter unit (FR-PU04/FR-PU07) is connected. When the
operation panel (FR-DU07) is connected, the above parameters can be set only when Pr. 160 User group read selection = "0". (Refer to page 308)
* When the setting of Pr. 21 Acceleration/deceleration time increments is "0" (initial value), the setting range is "0 to 3600s" and the setting increments are
"0.1s", and when the setting is "1", the setting range is "0 to 360s" and the setting increments are "0.01s"
(1) Jog operation from outside
⋅ When the JOG signal is ON, a start and stop can be made by the start signal (STF, STR). (The JOG signal is
assigned to the terminal JOG in the initial setting)
You can set the frequency and acceleration/deceleration time for Jog operation. Jog operation can be performed
from either the outside or PU.
Can be used for conveyor positioning, test operation, etc.
Parameter 
Number
Name
Initial 
Value
Setting Range
Description
15
 
Jog frequency
5Hz
0 to 400Hz
Set the frequency for Jog operation.
16
 
Jog 
acceleration/
deceleration 
time
0.5s
0 to 3600/360s*
Set the acceleration/deceleration time for Jog operation. Set the 
time taken to reach the frequency (Initial value is 60Hz) set in Pr. 20 
Acceleration/deceleration reference frequency
 for acceleration/
deceleration time. 
The acceleration and deceleration time cannot be set separately.
REMARKS
⋅ When you want to change the running frequency, change Pr. 15 Jog frequency . (initial value "5Hz")
⋅ When you want to change the acceleration/deceleration time change Pr. 16 Jog acceleration/deceleration time . (initial value
"0.5s")
Output 
frequency(Hz)
Pr.20
Pr.15 
Jog frequency
setting range
Pr.16
Forward 
rotation
Reverse 
rotation
Time
ON
ON
ON
JOG signal
Forward 
rotation STF
Reverse 
rotation STR
STF
10
2
5
JOG
Motor
Inverter
R/L
1
S/L
2
T/L
3
U
V
W
Connection diagram for external Jog operation
STR
Three-phase AC 
power supply
Forward rotation start
Reverse rotation start
JOG signal
SD
1.
Screen at power-ON
       Confirm that the External operation mode is selected.
       ([EXT] lit)
       If not displayed, press        to change to the 
       external [EXT] operation mode.
       If the operation mode still does not change, 
       set Pr. 79 to change to the External operation mode.
Indication
Operation
2.
Turn the JOG switch on.
ON
Forward 
  rotation
Forward 
  rotation
Reverse
 rotation
Reverse
 rotation
Rotates while ON
Stop
3.
Turn the start switch (STF or STR) on.
        The motor rotates while start switch 
        (STF or STR) is ON.
        Rotates at 5Hz. (Initial value of Pr. 15)
   
4.
Turn the start switch (STF or STR) off.
ON
OFF