Frequency setting by external terminals
(2) Jog operation from PU
⋅ Set the PU (FR-DU07/FR-PU07/FR-PU04) to the
jog operation mode. Operation is performed only
while the start button is pressed.
CAUTION
⋅ When Pr. 29 Acceleration/deceleration pattern selection= "1" (S-pattern acceleration/deceleration A), the acceleration/deceleration
time is the period of time required to reach Pr. 3 Base frequency.
⋅ The Pr. 15 setting should be equal to or higher than the Pr. 13 Starting frequency setting.
⋅ The JOG signal can be assigned to the input terminal using any of Pr. 178 to Pr. 189 (input terminal function selection). When terminal
assignment is changed, the other functions may be affected. Set parameters after confirming the function of each terminal.
⋅ During jog operation, the second acceleration/deceleration via the RT signal cannot be selected. (The other second functions
are valid. (Refer to page 235))
⋅ When Pr. 79 Operation mode selection = "4", push 
/
 of the PU (FR-DU07/FR-PU04/FR-PU07) to make a start or push
 to make a stop.
⋅ This function is invalid when Pr. 79 = "3".
⋅ Jog operation is invalid under position control.
♦ Parameters referred to 
⋅ Pr. 13 Starting frequency  
 Refer to page 175
⋅ Pr. 29 Acceleration/deceleration pattern selection  
 Refer to page 176
⋅ Pr. 20 Acceleration/deceleration reference frequency, Pr. 21 Acceleration/deceleration time increments  
 Refer to page 172
⋅ Pr. 79 Operation mode selection  
 Refer to page 313
⋅ Pr. 178 to Pr. 189 (input terminal function selection)   
 Refer to page 231
Motor
Inverter
R/L
1
S/L
2
T/L
3
U
V
W
FR-DU07
Three-phase AC 
power supply
1.
2.
 
6.
 
7.
 
8.
  
5.
 
9.
10.
Indication
Operation
Stop
The parameter 
number read 
previously 
appears.
Press        to choose the 
PU JOG operation mode.
3.
 Press        (or        ). 
4.
 Release        (or        ).
The monitor mode should have been selected.
The inverter should be at a stop.
While         (or        ) is pressed, the 
motor rotates.
Rotates at 5Hz. (initial value of Pr. 15)
Hold down.
Press         to set.
Flicker      Parameter setting complete!!
Release
Press         to choose the parameter 
setting mode.
Perform the operations in steps 1 to 4.
The motor rotates at 10Hz.
Turn          until Pr. 15 JOG frequency 
appears.
Turn         to set the value to 
"           ". (10Hz)
Press         to show the present set 
value. (5Hz)
Confirmation of the RUN indicator and 
operation mode indicator
[When changing the frequency of PU JOG 
operation]