F. Installation of Remote Condenser Unit
1. Checks Before Installation
1) Remove the shipping carton, tape, and packing material.
) Check that the refrigerant lines do not rub or touch lines or other surfaces, and that the 
fan blade moves freely.
2. Location
IMPORTANT
The remote condenser unit is intended for outdoor use. Normal operating 
ambient temperature should be within -0°F  to +1°F (-9°C to +50°C). 
Operation of the remote condenser unit, for extended periods, outside of this 
normal temperature range may affect icemaker performance.
The remote condenser unit must be positioned in a permanent site under the following 
guidelines:
• A firm and flat site.
• A dry and well ventilated area with 4" (61 cm) clearance in both front and rear for ease of 
maintenance and service should they be required.
• The maximum line length for the standard refrigerant charge is 66 feet. Should an 
installation require a longer line length, additional refrigerant must be added to the 
system. Add .4 oz. of R-404A for each foot over 66 feet to a maximum of 100 feet or call 
1-800-33-1940 for recommendations.
• The maximum vertical distance between the remote condenser unit and the icemaker is 
33 feet above or 10 feet below the icemaker. These distances are measured fitting to 
fitting.
CAUTION 
Failure to install the equipment within these guidelines may adversely affect 
performance, component life, and warranty coverage.
Fig. 4
Air
Air
Min. 4" (61 cm)
 
Clearance
Locate 
Legs