Configuration, Startup, and Operation 
 
 
of Recorder with Display 
12/03 
DR4300 Circular Chart Recorder Product Manual 
87 
Lower Display 
Prompt 
Upper Display  
Range of Setting  
or Selection 
Parameter  
Definition 
LD CAL 
 
 
FAC [factory setting] 
 
FLD 
LOAD CALIBRATION VALUES
—This parameter is used to specify 
which set of calibration values you want to use. 
Factory
—Uses built-in calibration values (stored in read-only 
memory). 
Field
—Uses calibration values stored as a result of the field 
calibration procedure described in Section 5. 
ATTENTION
 Until field calibration has been done,  
FLD uses the same calibration values as FAC. When field 
calibration is performed, the value of LD CAL is automatically set to 
FLD at the completion of the field calibration operation. 
INP HI 
 
 
–999 to 9999 
 
 [factory setting = 900] 
 
INPUT HIGH RANGE VALUE
 in engineering units is displayed but 
can only be configured for linear input type.  
Otherwise, this is a read-only display of the higher range value for 
the selected T/C or RTD input type.  
•  Scale the input signal to the display value you want for 100 %. 
•  EXAMPLE: 
  Actuation (Input) = 4 to 20 mA 
  Process Variable = Flow 
  Range of Flow = 0 to 250 Gal/Min 
  High Range display value = 250 
  Then 20 mA = 250 Gal/Min 
INP LO 
 
 
–999 to 9999 
in Engineering Units 
 
 [factory setting = 
300]
 
INPUT LOW RANGE VALUE
 in engineering units is displayed but 
can only be configured for linear input type. 
•  Otherwise, this is a read-only display of the low range value for 
the selected T/C or RTD input type. 
•  Scale the input signal to the display value you want for 0 %. See 
example in “INPHI”. 
BIAS 
–99.9 to 999.9 
 
 [factory setting = 0] 
INPUT BIAS
—Used to compensate the input for drift of an input 
value due to deterioration of a sensor, or some other cause; select 
the value you want on the input. 
FILTER  
 
0 to 120 seconds 
No filter = 0 
 
[factory setting = 0]
 
FILTER FOR INPUT
—A software digital filter is provided for the 
input to smooth the input signal. You can configure the first order 
lag time constant from 1 to 120 seconds. If you do not want filtering, 
enter 0.