Configuration, Startup, and Operation 
 
 
of Recorder with Display 
12/03 
DR4300 Circular Chart Recorder Product Manual 
85 
4.3.7  Input Parameters Set Up Group 
Introduction 
These are the parameters required to configure the temperature units, decimal location, actuation, high and 
low range values in engineering units, bias, filter, and burnout. For a 2-pen recorder, the desired input 
channel is displayed on the left side of the operator interface. 
Press FUNC  key to select channel. 
 
Input group prompts 
Table 4-5 lists all the function prompts in the input set up group. 
Press SETUP  key until “INPUT” appears in the lower display. 
Press FUNC  key to display the parameters. 
Table 4-5  Input Parameter Definitions 
Lower Display 
Prompt 
Upper Display  
Range of Setting  
or Selection 
Parameter  
Definition 
DECMAL
 
 
 
XXXX  [factory setting]
XXX.X 
XX.XX 
 
DECIMAL POINT LOCATION
—This selection determines where 
the decimal point appears in the display. 
None 
One Place 
Two Places 
NOTE: Be sure the selection agrees with the value to be displayed. 
If PV requires 4 whole digits, the decimal will not show. Value of “IN 
TYP” parameter must be for a linear input type for two decimal 
places to be displayed. 
UNITS 
 
 
NONE 
F         [factory setting]
TEMPERATURE UNITS
—This selection will be indicated on the PV 
display.  
No units 
Degrees Fahrenheit 
Degrees Celsius