Schneider Electric INTERBUS Basic Network Interface Module User Manual

Page of 71
Configuring the Island Bus
34
890USE19600 April 2004
Island Fallback Scenarios
Introduction
In the event of a communications failure on the island or between the island and the 
fieldbus, output data is put into a predefined fallback state so that the module’s 
values are known when the system recovers from the failure.
When you use a basic NIM, you cannot change the fallback parameters of any 
modules in the segment. All output channels on the modules go to a predefined 
fallback value of 0.
Fallback 
Scenarios
There are several scenarios in which Advantys STB output modules go into their 
fallback states:
l
loss of fieldbus communications—Communications with the fieldbus master are 
lost.
l
loss of island bus communications—There is an internal island bus 
communications error, indicated by a missing heartbeat message from either the 
NIM or a module.
l
change of operating state—The NIM may command the island I/O modules to 
switch from a running to a non-running (stopped or reset) state.
In all of these fallback scenarios, the NIM disables the heartbeat message.
Heartbeat 
Message
The Advantys STB system relies on a heartbeat message to ensure the integrity and 
continuity of communications between the NIM and the island modules. The health 
of island modules and the overall integrity of the Advantys STB system are 
monitored through the transmission and reception of these periodic island bus 
messages.
Because island I/O modules are configured to monitor the NIM’s heartbeat 
message, output modules will go into their fallback states if they do not receive a 
heartbeat message from the NIM within the defined interval.
Note: If a module fails, it needs to be replaced. The module may not go to its 
fallback state.