Fieldbus Communications Support
36
890USE19600 April 2004
The INTERBUS ID Code
Introduction
The ID cycle is part of the INTERBUS network’s initialization process. After 
determining the length of its own data during network initialization, every network 
device reports its functionality and byte length in the two-byte ID code. The 
INTERBUS ID code is a 16-bit word that describes the data type, data length and 
module type (digital/analog, input/output/mixed) of network devices.
The Low and 
High Bytes
Data type is transmitted in the ID code’s low byte; data length and message 
information are reported in the high byte: 
data type (03h, 33h)
data length (0 to 16 words)
messages (for management functions)
Data Type
The INTERBUS NIM recognizes one of two possible data types:
Data Type
Signal Direction
Signal Type
03h
input/output
digital
33h
input/output
analog or mixed