9.3 Installing 
the 
D8125 POPEX Module 
 
For information on the Multiplex Bus 
Interface, refer to the D8125MUX Multiplex 
Bus Interface Operation and Installation 
Guide
 (P/N: F01U034973). 
Save the POPIT Label Sheets: The D8125 is 
packaged with two sets of POPIT label sheets. One 
set is marked “Bank 1” for use with the D7412GV3 
and D7212GV3.  The other set is marked “Bank 2” for 
use with the D9412GV3 and D9112. Use the sheets 
later to label the POPITs. Refer to Section 9.3.6 
POPIT Module Point Assignments
 on page 42.  
9.3.1 Mounting 
To install the D8125 in the enclosure with the control 
panel: 
1.  Align the D8125 POPEX Module with any of the 
four mounting locations in the enclosure  
(Figure 2 on page 15). 
2.  Using the screws provided with the module, 
secure it in the enclosure. 
9.3.2  Wiring the D8125 to the Control Panel 
To wire one or two D8125 Modules to the control 
panel (Figure 16 on page 38 and Figure 17 on page 
39): 
Power Down the Control Panel: Disconnect the 
positive (red) battery lead at the battery and unplug 
the transformer. 
For Points 9 to 127 (9 to 75 on D7412GV3): 
1.  Connect the GND terminal of the D8125 to 
Terminal 23 on the D9412GV3 or to Terminal 9 
on the D7412GV3. 
2.  Connect the OUT terminal of the D8125 POPEX 
Module to ZONEX IN 1, Terminal 27.  
3.   Connect the IN terminal of the D8125 POPEX 
Module to ZONEX OUT 1, Terminal 28.  
4.  Connect the AUX terminal of the D8125 to 
Terminal 24 on the D9412GV3 or to Terminal 3 
on the D7412GV3. 
For Points 129 to 247 (D9412GV3 only): 
1.  Connect the GND terminal of the D8125 to 
Terminal 23. 
2.  Connect the OUT terminal of the D8125 POPEX 
Module to ZONEX IN 2, Terminal 25.  
3.   Connect the IN terminal of the D8125 POPEX 
Module to ZONEX OUT 2, Terminal 26.  
4.  Connect the AUX terminal of the D8125 to 
Terminal 24. 
Refer to Section 9.3.4 Wiring Data Expansion Loops 
to POPEX Modules
 on page 41 for instructions on 
connecting POPITs to the D8125 POPEX Module. 
9.3.3  Wiring POPITs to the Data Expansion 
Loop 
Use one two-wire data expansion loop or distribute 
the POPITs on up to three loops. Setting DIP 
switches on the POPIT Modules assigns them to point 
numbers. Refer to Section 9.3.6 POPIT Module Point 
Assignments
 on page 41. 
Review Section 4.6.2 Installing and Wiring Detection 
Devices 
on page 17 to determine if shielded wire is 
required. Refer to Table 13 to determine the wire 
gauge for the length of each data expansion loop. 
Table 13:  Data Expansion Loop Wire 
Specifications 
 
Maximum Length of All Data Expansion Loops 
Combined 
AWG 
Length in Meters (Feet) 
22 
548 (1800) 
20 881 
(2890) 
18 
1402 (4600) 
16 2231 
(7320) 
14 
3551 (11,650) 
Combine Data Expansion Loops 
The maximum lengths shown in Table 13 are for all 
data expansion loops connected to the same POPEX 
Module combined. 
Wiring POPITs Together 
 
Do not connect POPITs to each other in 
series or with a T-tap. Doing so might 
cause random missing POPIT conditions. 
 
 
Before installing the POPITs, ensure that 
the resistance on the data expansion loop 
is no more than 40 
. 
To connect POPITs to one another in parallel: 
1.  Connect the positive (+) data terminal from one 
POPIT to the positive (+) data terminal on the 
next POPIT. 
2.  Connect the negative (-) data terminal from one 
POPIT to the negative (-) data terminal on the 
next POPIT. 
3.  Repeat Steps 1 and 2 to connect all POPITs to 
the expansion loop. It is not necessary to wire the 
POPITs in any particular order on the loop. The 
switch setting on each POPIT assigns it a point 
number, regardless of its physical location. 
Three-inch Clearance for Tampered POPITs 
Mount tampered POPIT modules at least 7.6 cm (3 
in.) apart to prevent the tamper magnets from 
interfering with each other.