XR10/XR20 Installation Guide
UNIVERSAL UL BURGLARY SPECIFICATIONS
15.1 Introduction
The programming and installation specifications contained in this section must be completed when installing the
XR10/XR20 panel in accordance with any of the UL burglary standards. Additional specifications may be
required by a particular standard.
15.2 Wiring
All wiring must be in accordance with NEC, ANSI/NFPA 70,  UL 681,  and UL 611 for all burglary installations.
15.3 Police station phone numbers
The digital dialer telephone number programmed for communication must not be a police station phone number,
unless that phone number is specifically provided for that purpose.
15.4 Bypass reports
The bypass reports option must be programmed as YES for all UL burglary applications. See section 5.5 of the
XR10 Programming Guide (LT-0230) and XR20 Programming Guide (LT-0305).
15.5 System maintenance
Proper installation and regular maintenance by the installing alarm company and frequent testing by the end
user is essential to ensure continuous satisfactory operation of any alarm system. Offering  a maintenance
program and acquainting the user with the correct procedure for use and testing of the system is also the
responsibility of the installing alarm company.
15.6 Cross zoning
Zones used for cross zoning must be installed to allow detection of the same event. Cross zoning shall not
conflict with UL 681 or 1641.
15.7 Ground Start
Ground Start phone lines must not be used for UL listed systems.
15.8 UL Listed Receivers
UL has verified operation with the DMP SCS-1 Security Receiver, Sur-Gard SG-HLR2-DG, FBII CP220PB,
Osborne-Hoffman Quick-Alert and Radionics D6500 receivers.
UL 1023 SPECIFICATIONS
Household Burglar-Alarm System Units
16.1 Bell cutoff
The bell cutoff time cannot be less than five minutes. See section 7.2 of the XR10 Programming Guide (LT-0230)
and XR20 Programming Guide (LT-0305).
16.2 Entry delay
The maximum entry delay used must not be more than 45 seconds. See section 6.4 of the XR10 Programming
Guide (LT-0230) and XR20 Programming Guide (LT-0305).
16.3 Exit delay
The maximum exit delay used must not be more than 60 seconds. See section 6.5 of the XR10 Programming
Guide (LT-0230) and XR20 Programming Guide (LT-0305).
16.4 Zone expansion on 4-wire bus
When expansion zones are used, the keypad and zone
expander 4-wire bus must be limited to three feet in length
unless an external communication fail indicator is added. A
12 VDC relay may be wired as a communication fail
indicator. To install, connect the negative side of the
indicator to one of the panel's annunciator outputs and the
positive side to the smoke power (terminal 11 of the XR10/
XR20 panel). See section 7.5C of the XR10 Programming
Guide (LT-0230) and XR20 Programming Guide (LT-0305).
In addition to the wiring described above, a 24 hour zone must be programmed to activate the appropriate
annunciator output.