OPERATIONAL TESTS 
AND ADJUSTMENTS
sEctioN 5.1
sYstEm fuNctioNal tEsts
Part 5
Page 149
DANGER
+
 
  tHE traNsfEr sWitcH is NoW ElEctri-
callY “Hot”, coNtact WitH “Hot” Parts 
Will rEsult iN EXtrEmElY HaZarDous 
aND PossiBlY fatal ElEctrical sHocK. 
ProcEED WitH cautioN.
5.  Use  an  accurate  AC  voltmeter  to  check  utility  power 
source voltage across transfer switch Terminals N1 and 
N2. Nominal line-to-line voltage should be 240 volts AC.
6.  Check utility power source voltage across Terminals N1 
and the transfer switch neutral lug; then across Terminal 
N2  and  neutral.  Nominal  line-to-neutral  voltage  should 
be 120 volts AC.
7.  When  certain  that  utility  supply  voltage  is  compatible 
with transfer switch and load circuit ratings, turn off the 
utility power supply to the transfer switch.
8.  On  the  generator  panel,  set  the  AUTO-OFF-MANUAL 
switch to MANUAL. The engine should crank and start.
9.  Let the engine warm up for about five minutes to allow 
internal temperatures to stabilize. Then, set the generator 
main circuit breaker to its “ON” (or closed) position.
DANGER
+
   ProcEED WitH cautioN! GENErator 
PoWEr VoltaGE is NoW suPPliED to 
tHE traNsfEr sWitcH. coNtact WitH 
liVE traNsfEr sWitcH Parts Will 
rEsult iN DaNGErous aND PossiBlY 
fatal ElEctrical sHocK.
10. Connect  an  accurate  AC  voltmeter  and  a  frequency 
meter across transfer switch Terminal Lugs E1 and E2. 
Voltage should be 242-252 volts; frequency should read 
about 61-63 Hertz (7/8 kW units) and about 60 Hertz on 
10-20 kW units.
11. Connect  the  AC  voltmeter  test  leads  across Terminal 
Lug E1 and neutral; then across E2 and neutral. In both 
cases, voltage reading should be 121-126 volts AC.
12. Set the generator main circuit breaker to its OFF (or open) 
position. Let the engine run at no-load for a few minutes to 
stabilize internal engine generator temperatures.
13. Set  the  generator  AUTO-OFF-MANUAL  switch  to  OFF. 
The engine should shut down.
note: it is important that you do not proceed until 
you are certain that generator ac voltage and fre-
quency  are  correct  and  within  the  stated  limits. 
Generally,  if  both  ac  frequency  and  voltage  are 
high  or  low,  the  engine  governor  requires  adjust-
ment.  if  frequency  is  correct,  but  voltage  is  high 
or  low,  the  generator  voltage  regulator  requires 
adjustment.
Generator teStS under load
To test the generator set with electrical loads applied, 
proceed as follows:
1.  Set  generator  main  circuit  breaker  to  its  OFF  (or 
open) position.
2.  Turn  OFF all  loads  connected  to  the Transfer  Switch 
Terminals T1 and T2.
3.  Set the generator AUTO-OFF-MANUAL switch to OFF.
4.  Turn  off  the  utility  power  supply  to  the  transfer  switch, 
using  the  means  provided  (such  as  a  utility  main  line 
circuit breaker).
+
   Do Not attEmPt maNual traNsfEr 
sWitcH oPEratioN uNtil all PoWEr 
VoltaGE suPPliEs to tHE traNsfEr 
sWitcH HaVE BEEN PositiVElY turNED 
off. failurE to turN off all PoWEr 
VoltaGE suPPliEs Will rEsult iN 
EXtrEmElY HaZarDous aND PossiBlY 
fatal ElEctrical sHocK.
5.  Manually set the transfer switch to the STANDBY posi-
tion,  i.e.,  load  terminals  connected  to  the  generator 
E1/E2  terminals. The  transfer  switch  operating  lever 
should be down.
6.  Set  the  generator  AUTO-OFF-MANUAL  switch  to 
MANUAL. The engine should crank and start immediately.
7.  Let the engine stabilize and warm up for a few minutes.
8.  Set  the  generator  main  circuit  breaker  to  its  ON  (or 
closed) position. Loads are now powered by the standby 
generator.
9.  Turn ON electrical loads connected to transfer switch T1 
and T2. Apply an electrical load equal to the full rated 
wattage/amperage capacity of the installed generator.
10. Connect  an  accurate  AC  voltmeter  and  a  frequency 
meter across Terminal Lugs E1 and E2.
a.  7/8kW voltage should be greater than 230 volts 
and frequency should be greater than 58 Hz.
b.  10-20  kW  voltage  should  be  greater  than  240 
volts and frequency should be 
60 Hz.