Generac Power Systems 16 kW NG User Manual

Page of 192
•  An open circuit condition
•  A “short-to-ground” condition
•  A short circuit between windings
note: the  resistance  of  stator  windings  is  very  low. 
Some  meters  will  not  read  such  a  low  resistance, 
and will simply indicate continuity. recommended 
is  a  high  quality,  digital  type  meter  capable  of  read-
ing very low resistances.
PROCEDURE, 8 kW:
1.  Disconnect Stator Leads 11 and 44 from the main circuit 
breaker.
2.  Disconnect  Stator  Leads  22  and  33  from  the  neutral 
connection separate the leads.
3.  Make  sure  all  of  the  disconnected  leads  are  isolated 
from each other and are not touching the frame during 
the test.
4.  Set a VOM to measure resistance.
5.  Connect  one  test  lead  to  Stator  Lead  11.  Connect  the 
other  test  lead  to  Stator  Lead  22.  Note  the  resistance 
reading and compare to the specifications in the front of 
this manual.
6.  Connect  one  test  lead  to  Stator  Lead  33.  Connect  the 
other  test  lead  to  Stator  Lead  44.  Note  the  resistance 
reading and compare to the specifications in the front of 
this manual.
PROCEDURE, 10 kW:
1.  Isolate  the  generator  from  the  transfer  switch  by  dis-
connecting the load wires from the main breaker inside 
the generator.
2.  Disconnect  Stator  Leads  22  and  33  from  the  neutral 
connection and separate the leads.
3.  Make  sure  all  of  the  disconnected  leads  are  isolated 
from each other and are not touching the frame during 
the test.
4.  Turn the Main Breaker to the "ON" or CLOSED position.
5.  Set a VOM to measure resistance.
6.  See Figure 4 for proper testing points.
 Connect one 
meter test lead to Wire 11 on the load side of the main 
breaker.  Connect  the  other  meter  test  lead  to Wire  22 
(power winding). Note the resistance reading and com-
pare to the specifications in the front of this manual.
7.  Connect  one  test  lead  to  Stator  Lead  44  on  the  load 
side  of  the  main  breaker.  Connect  the  other  test  lead 
to Stator Lead 33 (power winding). Note the resistance 
reading and compare to the specifications in the front of 
this manual.
note: Wire  11  and Wire  44  could  be  switched  on 
the  main  breaker.  if  an  inFinity  reading  is  indi-
cated  try  putting  the  meter  leads  on  the  other 
output terminal of the breaker. if inFinity is still 
read then an actual fault may exist.
TEST WINDINGS FOR A SHORT TO GROUND:
7.  Make sure all leads are isolated from each other and are 
not touching the frame.
8.  Connect one test lead to a clean frame ground. Connect 
the other test lead to stator lead Wire 11.
a.  The meter should read INFINITY.
b.  Any  reading  other  than  INFINITY  indicates  a 
“short to ground” condition.
9.  Repeat Step 7 using stator lead 44
TEST FOR A SHORT CIRCUIT BETWEEN WINDINGS:
10. Connect  one  test  lead  to  stator  lead  11.  Connect  the 
other test lead to stator lead 33.
a.  The meter should read INFINITY.
b.  Any  reading  other  that  INFINITY  indicates  a 
short between windings.
11. Repeat Step 10 using Wire 44.
RESULTS:
1.  Stator winding resistance values is a test of winding conti-
nuity and resistance. If a very high resistance or INFINITY 
is indicated, the winding is open or partially open.
2.  Testing  for  a  “grounded”  condition:  Any  resistance 
reading indicated the winding is grounded.
3.  Testing for a “shorted” condition: Any resistance reading 
indicated the winding is shorted.
4.  If stator tests good and wire continuity tests good, refer 
back to flow chart.
teSt 9 – check capacitor
DISCUSSION:
The brushless rotor system relies on the charging and 
discharging  of  a  capacitor  to  induce  voltage  into  the 
rotor  and  also  to  regulate  voltage  once  240  VAC  is 
achieved. If the capacitor fails, only residual magnetism 
of the rotor will be measured at the Main Breaker.
*
   Danger: the capacitor may need to be dis-
charged before testing. a capacitor can be 
discharged by crossing the terminals with 
a metal insulated screw driver.
*
   Danger: use proper protective equipment 
when dealing with a capacitor that has 
exploded.
Page 46
Part 2
AC GENERATORS
sEctioN 2.4
DiaGNostic tEsts