AC GENERATORS
sEctioN 2.4
DiaGNostic tEsts
PROCEDURE:
1.  Consult the owner’s manual of the meter being used for 
directions on measuring capacitance. Figure 7 shows a 
typical meter and how to check capacitance.
2.  Connect the meter leads directly across the terminals of 
the capacitor. The rated 
µf (micro farad) of the capacitor 
is marked on the side of the canister.
3.  The meter should display the correct 
µf reading ± 5µf
If anything other than the indicated rating is displayed, 
replace the capacitor.
Figure 6. Capacitor
SET TO READ
CAPACITANCE
CAPACITOR
+
+
-
-
59.0 
µf
 
Figure 7. Field Boost Test Points
RESULTS:
1.  Refer back to flow chart
2.  Common  observations  can  be  made  by  visually 
inspecting the capacitor.
a.  A  capacitor  that  has  gone  bad  can  have  a 
tendency to explode. Use caution when deal-
ing  with  an  exploded  capacitor,  the  gel  from 
inside a capacitor can cause skin irritation.
b.  A  capacitor  is  defective  if  the  terminal  connec-
tions are loose on the canister.
c.  A capacitor is defective if it wobbles while sitting 
on a flat surface.
d.  If any of the above observations are observed, 
replace the capacitor.
teSt 10 – teSt dpe WindinG on 
BruShleSS unitS
DISCUSSION:
A  DPE  winding  or  Displaced  Phase  Excitation  wind-
ing  is  used  to  charge  a  capacitor  that  discharges  and 
charges  releasing  a  voltage  that  is  induced  into  the 
rotor. If the DPE winding fails, only residual magnetism 
of the rotor will be measured at the Main Breaker.
note: the  resistance  of  stator  windings  is  very 
low.  Some  meters  will  not  read  such  a  low  resis-
tance,  and  will  simply  indicate  continuity. 
recommended is a high quality, digital type meter 
capable of reading very low resistances.
*
  Warning: the capacitor may need to be 
discharged before testing. a capacitor can 
be discharged by crossing the terminals 
with a metal insulated screw driver.
PROCEDURE:
1.  Disconnect Wire 2 and Wire 6 from the capacitor.
2. 
Set VOM to measure resistance.
3.  Connect one meter lead to Wire 2 and connect the other 
meter lead to Wire 6.
a.  Refer  to  the  specifications  in  the  front  of  this 
manual for the correct resistance reading.
4.  Connect one meter lead to Wire 2 and connect the other 
meter lead to a clean frame ground, INFINITY should be 
measured.
5.  Disconnect Wires  11  and  44  from  the  main  line  circuit 
breaker.
6.  Disconnect Wire 22 and Wire 33 from the neutral connection
note: isolate all main stator leads before proceeding.
7.  Connect one meter lead to Wire 2 and connect the other 
meter lead to Wire 11. INFINITY should be measured.
8.  Repeat Step 7 using Wires 2 and 44.
RESULTS:
1.  Stator winding resistance values is a test of winding conti-
nuity and resistance. If a very high resistance or INFINITY 
is indicated, the winding is open or partially open.
Part 2
Page 47