Honeywell 301C User Manual

Page of 107
Honeywell 301C User Manual 
420MDBS_IR-F9  
93 
 
Property
Data Type
Required
1
Storage 
Type
2
BACnet 
Writeable?
Value
object_identifier
R
C
N
Modbus address * 256 + 1.  For example an 
420MDBS at Modbus address 002 will 
appear as 513 or 0x0201.
object_type
enumerated
R
C
N
analog_input (0)
event_state
enumerated
R
R
N
if gas sensor fault Fault (1),
else normal (0)
object_name
character string
R
N
N
"420MDBS GGGG   AdXXX .GGGG" where 
GGGG is the gas name and XXX  is the 
Modbus address.  Values for gas name 
include "NH3".
out_of_service
boolean
R
R
N
FALSE
present_value
real
R
R
N
Gas reading
an
al
og
_i
n
gas
reliability
enumerated
O
R
N
As appropriate reports
no_fault_detected (0) or
unreliable other (7)
status_flags
in_alarm
boolean
R
R
N
if alarm or fault "true" (1)
else "false" (0)
fault
boolean
R
R
N
if faulty "true" (1)
else "false" (0)
overridden
boolean
R
R
N
"false" (0)
out_of_service boolean
R
R
N
"false" (0)
units
enumerated
R
N
N
Depends on configuration of 420MDBS 
factory configuration or 301C configuration, 
usually ppm (96)
Notes
1  --  'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --  'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
continued…
Group