Honeywell 301C User Manual

Page of 107
Honeywell 301C User Manual 
 
Property
Data Type
Required
1
Storage 
Type
2
BACnet 
Writeable?
Value
object_identifier
R
N
N
Modbus address * 256 + 4.  For example an 
420MDBS at Modbus address 002 will 
appear as 516 or 0x0204.
object_type
enumerated
R
C
N
analog_value (2)
event_state
enumerated
R
C
N
normal (0)
object_name
character string
R
N
N
"420MDBS GGGG   AdXXX .Amin" where 
GGGG is the gas name and XXX  is the 
Modbus address.  Values for gas name 
include "NH3".
out_of_service
boolean
R
C
N
FALSE
present_value
real
R
N
Y
Gas threshold from 301C.  Synchronization 
is maintained with the 301C and the 
420MDBS.  Whichever value is written last 
is distributed to the other two locations.
reliability
enumerated
O
C
N
no_fault_detected (0)
status_flags
in_alarm
boolean
R
C
N
always false (0)
fault
boolean
R
C
N
always false (0)
overridden
boolean
R
C
N
always false (0)
out_of_service boolean
R
C
N
always false (0)
units
enumerated
R
C
N
Depends on configuration of 420MDBS 
factory configuration or 301C configuration, 
usually ppm (96)
object_identifier
R
N
N
Modbus address * 256 + 5.  For example an 
420MDBS at Modbus address 002 will 
appear as 517 or 0x0205.
object_type
enumerated
R
C
N
analog_value (2)
event_state
enumerated
R
C
N
normal (0)
object_name
character string
R
N
N
"420MDBS GGGG   AdXXX .Amin" where 
GGGG is the gas name and XXX  is the 
Modbus address.  Values for gas name 
include "NH3".
out_of_service
boolean
R
C
N
FALSE
present_value
real
R
N
Y
Gas threshold from 301C.  Synchronization 
is maintained with the 301C and the 
420MDBS.  Whichever value is written last 
is distributed to the other two locations.
reliability
enumerated
O
C
N
no_fault_detected (0)
status_flags
in_alarm
boolean
R
C
N
always false (0)
fault
boolean
R
C
N
always false (0)
overridden
boolean
R
C
N
always false (0)
out_of_service boolean
R
C
N
always false (0)
units
enumerated
R
C
N
Depends on configuration of 420MDBS 
factory configuration or 301C configuration, 
usually ppm (96)
Notes
1  --  'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --  'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
Group
An
al
og
 V
al
ue
s
Bm
in
Bm
ax
95