1 Install and cable a G600 cabinet
Section I – S8100 with a G600 installation
58
S8100 Installation and Upgrades
November 2003
Section I – S8100 with a G600 installation
This section covers procedures for installing the S8100 server with the G600 Media Gateway.
Site requirements
A G600 mounts in a standard 19-inch (48-cm) data rack that has been properly preinstalled and secured 
per local code and the EIA 310 (or equivalent) standards. The customer is responsible for providing the 
rack and having it installed and secured prior to G600 installation. This also applies to providing AC 
power to the rack and approved grounding. Technicians who are trained to install G600s do not typically 
have the tools or proper training to install data racks.
If floor-mounted (single cabinet only), the technician is responsible for installing the cabinet per local 
code.
The G600 cabinet’s dimensions are 12 inches (7µ) high × 22 inches deep × 19 inches wide. The G600 
cabinet can be mounted at its midpoint by removing the mounting brackets and remounting them at a 
medial position.
Installation requires 1 foot (30 cm) of clearance in the rear, and 18 inches (45 cm) of clearance in the 
front, which is consistent with the EIA 310 data rack standards. In a 2- or 3-cabinet configuration, the 
dimensions of the TDM/LAN cable require that one cabinet be mounted directly over the other (flush).
The G600 should be installed in a well-ventilated area. Maximum equipment performance is achieved at 
an ambient temperature between 40 and 120° F (4 and 49° C) for short-term operation (no more than 72 
consecutive hours or 15 days in a year) and up to 110° F (43° C) for continuous operation. The relative 
humidity range is 10 to 95% at up to 84° F (29° C). Above this, maximum relative humidity decreases 
from 95% down to 32% at 120° F (49° C). Installations outside these limits may reduce system life or 
affect operation. The recommended temperature and humidity range is 65 to 85° F (18 to 29° C) at 20 to 
60% relative humidity.