Power-Related Hardware 
3
Protection Accessories
3
This section describes accessories that are needed for grounding and protecting 
special telephone connections from power surges, electromagnetic interference, 
and electrostatic discharge.
In-Range Out-of-Building Protection
3
Your Lucent Technologies representative orders an In-Range Out-of-Building 
(IROB) protection unit when equipment is connected to the following jacks and is 
located in a different building but within 1000 feet (305 m) of the control unit:
Analog multiline telephone extension jacks on 008, 408, and 408 GS/LS 
modules
MLX telephone extension jacks on 008 MLX or 408 GS/LS-MLX modules
These units protect the equipment and the control unit from lightning strikes and 
power surges. Each piece of equipment requires two units, one for the control unit 
end of the wire run, the other for the equipment end.
CAUTION:
!
The IROB protectors must be installed by a qualified service technician or 
installer.
Off-Premises Range Extender
3
An Off-Premises Range Extender (OPRE) is used for off-premises extensions up 
to 5.2 miles from the control unit.
146A and 147A Surge Protectors
3
If you work in an area prone to heavy lightning and/or power surges, the control 
unit may require surge protectors. The control unit’s power supply has built-in 
protection, so extra protectors are not usually necessary. It is the responsibility of 
the local telephone company to provide primary protection on the outside lines 
where they connect to the control unit and to ensure that these protectors are 
properly grounded. If the telephone company line protector is properly grounded 
and bonded to the AC power ground, most lightning damage is prevented.
When your system is installed, your Lucent Technologies representative sees that 
you have the necessary protection. If electrical conditions change, contact your 
representative and ask for advice.