MICROMASTER  Applications Handbook 
 
7.2.3 
Key Parameter Details 
Table 7-2 
Fan Application with Closed Loop Control 
Number Value  Meaning 
P1000 
Digital set point preset in MIDIMASTER.  Manual adjustment not normally 
required. 
P1040 20  Nominal 
setpoint 
P0003 
Allows all parameters to be adjusted and set. 
P1080 
10 
Minimum fan speed 
P1082 30  Maximum 
fan 
speed 
P0778 
4.00 
Analog output 4 – 20 mA indicating output frequency.  This signal is used as 
part of the overall factory management system.  Setting P0778 applies a 
4 mA offset. 
P1300 
Quadratic V/F curve selected.  Selecting the quadratic curve allows a higher 
continuous output, but limits the overload capability, which is not needed in 
this case.  The quadratic curve also reduces the power consumption 
because it is optimised for fan and pump applications. 
P0300-
P0311 
*** 
Settings to suit motor 
P201 
PID enabled.  The following parameters give the best overall stability in this 
particular application. 
P202 0.3  P 
Gain 
P203 0.06 I 
Gain 
P204 0  D 
Gain 
P205 1  Sample 
Interval 
P206 0  Sensor 
Filtering 
P207 
100 
Integral capture range 
P208 1  Sensor 
type 
P211 
25 
0% set point 
P212 
80 
100% set point 
P220 
Switch off at minimum frequency 
P0761 
PI analog input  4 –20 mA to suit flow transducer