3  Commissioning
Issue A1
MICROMASTER 410    Operating Instructions
36
6SE6400-5EA00-0BP0
3.2.4.1 
Commissioning with the Operator Panel
The Operator Panel (OP) provides access to the inverter
parameters and enables the user to customize the
settings of your MICROMASTER 410. The OP can be
used to configure several MICROMASTER 410 Inverters.
This is accomplished by using the OP to set the required
parameters and once the process is complete, then the
OP can be removed.
The OP contains a five-digit display that allows the user to
read and change parameter values. The OP does not
have the capability to store parameter information.
Table 3-2 shows the factory default settings for operation via the Operator Panel.
Notes
  The OP motor control functions are disabled by default. To control the motor
via the OP, parameter P0700 should be set to 1 and P1000 set to 1.
  The OP can be fitted to and removed from the inverter whilst power is
applied.
  If the OP has been set as the I/O control (P0700 = 1), the drive will stop if the
OP is removed.
Table 3-2
Default settings for operation using the OP
Parameter
Meaning
Default
P0100
Operating Mode Europe/US
50 Hz, kW
P0307
Power (rated motor)
Dimension (kW (Hp)) depending on setting of P0100.
[default value depending on variant.]
P0310
Motor frequency rating
50 Hz (60 Hz) depending on setting of P0100.
P0311
Motor speed rating
1395 (1680) rpm; depending on setting of P0100.
[default value depending on variant]
P1082
Maximum Motor Frequency
50 Hz (60 Hz) depending on setting of P0100.