3  Commissioning
Issue A1
MICROMASTER 410    Operating Instructions
34
6SE6400-5EA00-0BP0
3.2.1 
Commissioning without an Operator Panel
The inverter is supplied with an LED to indicate the operation state of the unit.
The inverter can be used with its default settings, for a number of applications. The
default settings are shown in Table 3-1.
The terminal layout is shown in the photograph of the Control Terminal
Connections on the inside of the back cover of this manual.
Table 3-1
Default settings for operation using the standard inverter
Terminals
Parameter Default
Default Operation
Digital Input 1
1
P0701 = ‘1’
ON/OFF1
Digital Input 2
2
P0702 = ‘12’
Reverse
Digital Input 3
3
P0703 = ‘9’
Fault Acknowledge 
Warnings and faults states on the Inverter
The LED indicates the operating status of the inverter. The LED also indicate
various warnings or fault states. In section 6.1 on page 57 the inverter states,
indicated by the LED are explained.
3.2.2 Basic 
operation
With the default settings of the inverter the following is possible:
Ø  Start and stopping the motor (DIN1 via external switch)
Ø  Reversing the motor (DIN2 via external switch)
Ø  Fault Acknowledgement (DIN3 via external switch)
Controlling the speed of the motor is accomplished by connecting the analog inputs
as shown in the Figure 3-3 (Switches and potentiometers are not supplied with the
inverter).
Figure 3-3
Basic operation