Levelmaster Parameter Configuration Example
You want to use address 2 for the 5300/5400 transmitter and the host uses 
the following parameters:
Table 1-7.  Parameters Used by the 
Host (in case of Levelmaster, 
example)
To configure the 5300/5400 transmitter to communicate with the Host in this 
example, the following text string is written to the Modbus Message area.
HMC M2 A2 B9600 D7 PN S1.
NOTE
Include all the parameters when writing to the message area.
Note that an address must be unique on the bus.
HMC: These three letters are used for safety and will eliminate the risk of 
changing the configuration data by mistake.
M2: This means that the Levelmaster protocol is to be used.
A2A indicates that the following is the new address (address 2). Leading 
zeroes are not needed.
B9600B indicates that the following number is the new baud rate (1200, 
2400, 4800, 9600, 19200).
D7D indicates that the following data bits are to be used (7 = seven, 
8 = eight).
PNP identifies the following letter as parity type (O = odd, E = even, and 
N = none).
S1S indicates that the following figure is the number of stop bits (1 = one, 
2 = two).
Note: Start Bits are not configurable and cannot be set.
Parameter
Value
Baud Rate
9600
Start Bits
One
Data Bits
Seven
Parity
None
Stop Bits
One