Rosemount 5300/5400 Series
1-16
Using a Field 
Communicator to change 
communication 
parameters
NOTE
To change Modbus communication parameters, the Rosemount 5300/5400 
must use HART address 1, the default address.
NOTE
After changing communication parameters, disconnect the Field 
Communicator and wait up to 60 seconds for the change to take effect.
The Modbus communication parameters can be changed by entering a text 
string in the HART Message parameter. See separate sections below for 
details regarding each Modbus protocol and what strings to use.
When using the Field Communicator, the Message Area is reached using 
HART command [2,2,1], and then selecting Message (menu item 11 for 
Rosemount 5300 and menu item 10 for Rosemount 5400).
Modbus RTU 
Communication Setup
The Rosemount 5300/5400 is configured with the default Modbus RTU 
address 246, and with the following Modbus RTU communication parameter 
default settings:
Table 1-4.  Modbus RTU 
Communication Parameters
To reset the communication parameters to default Modbus RTU settings, use 
the following Modbus Message:
HMC
Modbus RTU Parameter Configuration Example
You want to use address 44 for the 5300/5400 transmitter, and the following 
communication parameters are used by the host:
Table 1-5.  Communication 
Parameters Used by the Host 
(example)
Parameter
Default Value
Configurable Values
Baud Rate
9600
1200, 2400, 4800, 9600, 19200
Start Bits
(1)
(1) Start Bits and Data Bits cannot be changed.
One
One
Data Bits
(1)
Eight
Eight
Parity
None
None, Odd, Even
Stop Bits
One
One or Two
Address 
range
246
1-255
Parameter
Value
Baud Rate
4800
Start Bits
One
Data Bits
Eight
Parity
Odd
Stop Bits
Two