Rosemount 5300/5400 Series
1-6
Connection Terminals
The connection terminals are described in Table 1-1 below:
Table 1-1.  Connection Terminals
Figure 1-3. Connection Terminals 
for Rosemount 5300/5400 with 
HART to Modbus Converter
Connector label
Description
Comment
HART +
Positive HART connector
Connect to PC with RRM 
software, Field 
Communicator, or other 
HART configurators.
HART -
Negative HART connector
MA
Modbus RS-485 B connection 
(RX/TX+)
(1)
(1) The designation of the connectors do not follow the EIA-485 standard, which states 
that RX/TX- should be referred to as 'A' and RX/TX+ as 'B'.
Connect to RTU
MB
Modbus RS-485 connection 
(RX/TX-)
POWER +
Positive Power input terminal
Apply +8 Vdc to +30 Vdc 
(max. rating)
POWER -
Negative Power input terminal
MODBUS
POWER
HART
(RS-485)
HART to Modbus Converter
MB
MA
Ambients > 60 ºC
Use wiring rated
for min 90 ºC
-
-
+
+
HART 
+
HART 
-