Alternatively, the Rosemount 5300/5400 Series Transmitters can be installed 
as shown in Figure 1-5. If this wiring layout is used, there is an increased risk 
for communication disturbances due to differences in potential between 
grounding points. By using the same grounding point for Modbus Master and 
Power Supply, this risk is reduced.
Figure 1-5. Alternative Multidrop 
Connection of 5300/5400 
Transmitters
Star Topology
For a Star Topology Connection of the 5300/5400 transmitters, the transmitter 
with the longest cable run needs to be fitted with a 120-
 termination resistor.
Figure 1-6. Star Topology 
Connection of 5300/5400 
Transmitters
MODBUS
POWER
HART
(RS-485)
HART to Modbus Converter
MB
MA
-
-
+
+
MODBUS
POWER
HART
(RS-485)
HART to Modbus Converter
MB
MA
-
-
+
+
Ambients > 60 ºC
Use wiring rated
for min 90 ºC
Ambients > 60 ºC
Use wiring rated
for min 90 ºC
Power 
Supply
120
120
RS-485 Bus
B
A
Modbus 
Master
Z
External 
Ground Screw
External 
Ground Screw
Internal
Ground Screw
Internal
Ground Screw
MODBUS
POWER
HART
(RS-485)
HART to Modbus Converter
MB
MA
-
-
+
+
MODBUS
POWER
HART
(RS-485)
HART to Modbus Converter
MB
MA
-
-
+
+
MODBUS
POWER
HART
(RS-485)
HART to Modbus Converter
MB
MA
-
-
+
+
MODBUS
POWER
HART
(RS-485)
HART to Modbus Converter
MB
MA
-
-
+
+
MODBUS
POWER
HART
(RS-485)
HART to Modbus Converter
MB
MA
-
-
+
+
MODBUS
(RS-485)
verter
MB
MA
-
Ambients > 60 ºC
Use wiring rated
for min 90 ºC
Ambients > 60 ºC
Use wiring rated
for min 90 ºC
Ambients > 60 ºC
Use wiring rated
for min 90 ºC
Ambients > 60 ºC
Use wiring rated
for min 90 ºC
Ambients > 60 ºC
Use wiring rated
for min 90 ºC
For Star Topology 
connection, 
connect the 120
termination 
resistor to the 
transmitter with 
the longest cable 
run.