Honeywell UDC 3300 Manual De Usuario

Descargar
Página de 294
4/00
UDC 3300 Controller Product Manual
217
SP programming tips
Table 6-4 gives procedures for restarting, advancing, and changing the
current segment time or setpoint of a running setpoint program.
Table 6-4
Procedures for Changing a Running Setpoint Program
Function
Press
Result/Action
Restarting a running
SP program
RUN 
HOLD
to place SP PROG into HOLD mode.
LOWER 
DISPLAY
until you see X RA XXX or X SK XX.XX in
the lower display.
until you see 1 RA XX.XX in the lower
display.
If the lower display already reads 1 RA
XX.XX
 then press the [
] key before
pressing the [
] key.
RUN 
HOLD
to place SP PROG into RUN mode.
Advancing a running
SP program
RUN 
HOLD
to place SP PROG into HOLD mode.
LOWER 
DISPLAY
until you see X RA XXX or X SK XX.XX in
the lower display.
 and 
together
to select the segment number to advance to.
EXAMPLE: Change 2 SK XX.XX to 3 RA
XX.XX
.
RUN 
HOLD
to place SP PROG into RUN mode.
Changing the
current segment
time or setpoint in a
running SP program
RUN 
HOLD
to place SP PROG into HOLD mode.
Enter SP PROG configuration and change
the segment to the new time or setpoint
desired.
LOWER 
DISPLAY
until you see X RA XXX or X SK XX.XX in
the lower display.
 then 
RUN 
HOLD
to place SP PROG into RUN mode.