American Water Heater 317994-002 Manual De Usuario

Descargar
Página de 36
11
TABLE 3
BTUH Input
Minimum 
Square
Feet with
8’ Ceiling
Typical Room
with 8’ Ceiling
30,000
188
9 x 21
45,000
281
14 x 20
60,000
375
15 x 25
75,000
469
15 x 31
90,000
563
20 x 28
105,000
657
20 x 33
120,000
750
25 x 30
135,000
844
28 x 30
IMPORTANT:
• 
The area must be open and be able to provide the 
proper air requirements to the water heater. Areas that 
are being used for storage or contain large objects 
may not be suitable for water heater installation. 
• 
Water heaters installed in open spaces in buildings 
with unusually tight construction may still require out-
door air to function properly. In this situation, outside 
air openings should be sized the same as for a con-
fined space. 
• 
Modern home construction usually requires supplying 
outside air into the water heater area. 
Confined Space                                                    
 
For the correct and proper operation of this water heater, 
ample air must be supplied for the combustion, ventilation, 
and dilution of flue gases. Small enclosures and confined 
areas must have two permanent openings so that sufficient 
fresh air can be drawn from outside of the enclosure. One 
opening shall be within 12 inches of the top and one within 
12 inches of the bottom of the enclosure as shown in 
Figure 4.
The size of each opening (free area) is determined by the 
total BTUH input of all gas utilization equipment (i.e., water 
heaters, furnaces, clothes dryers, etc.) and the method by 
which the air is provided. The BTUH input can be found 
on the water heater rating plate. Additional air can be 
provided by two methods:
1.   All air from inside the building.
2.   All air from outdoors.
COMBUSTION AIR & VENTILATION
WARNING
Carbon Monoxide Warning
Water heater must be vented to outdoors.
Vent must be installed by a qualified technician using 
the installation instructions.
Examples of a qualified technican include: gas 
technicians, authorized gas company personel, and 
authorized service persons.
Failure to so do can result in death or carbon monoxide 
poisoning.
IMPORTANT:  Air for combustion and ventilation must not 
come from a corrosive atmosphere. Any failure due to 
corrosive elements in the atmosphere is excluded from 
warranty coverage.
The following types of installation (not limited to the 
following) will require outdoor air for combustion due to 
chemical exposure and may reduce but not eliminate the 
presence of corrosive chemicals in the air:
• beauty 
shops
• 
photo processing labs
• 
buildings with indoor pools 
• 
water heaters installed in laundry, hobby, or craft 
rooms
• 
water heaters installed near chemical storage areas
Combustion air must be free of acid-forming chemicals such 
as sulfur, fluorine, and chlorine. These elements are found 
in aerosol sprays, detergents, bleaches, cleaning solvents, 
air fresheners, paint, and varnish removers, refrigerants, 
and many other commercial and household products. When 
burned, vapors from these products form highly corrosive acid 
compounds. These products should not be stored or used 
near the water heater or air inlet.
Combustion and ventilation air requirements are determined 
by the location of the water heater. The water heater may 
be located in either an open (unconfined) area or in a 
confined area or small enclosure such as a closet or small 
room. Confined spaces are areas with less than 50 cubic 
feet for each 1,000 BTUH of the total input for all gas-using 
appliances.
Unconfined Space                                                   
A water heater in an unconfined space uses indoor air for 
combustion and requires at least 50 cubic feet for each 
1,000 BTUH of the total input for all gas appliances. The 
table below shows a few examples of the minimum square 
footage (area) required for various BTUH inputs.