American Water Heater 317994-002 Manual De Usuario

Descargar
Página de 36
12
12” Max.
Permanent
openings to 
the outside or
additional 
rooms within 
the building
Closet
or other
confined
space
12” Max.
FIGURE 4.
All Air from Inside the Building                              
When additional air is to be provided to the confined area 
from additional room(s) within the building, the total volume 
of the room(s) must be of sufficient size to properly provide 
the necessary amount of fresh air to the water heater 
and other gas utilization equipment in the area. If you are 
unsure that the structure meets this requirement, contact 
your local gas utility company or other qualified agency for 
a safety inspection. 
Each of the two openings shall have a minimum free area 
of 1 square inch per 1,000 BTUH of the total input rating of 
all gas utilization equipment in the confined area, but not 
less than 100 square inches (Figure 5).
FIGURE 5.
All Air from Outdoors                                           
Outdoor fresh air can be provided to a confined area either 
directly or by the use of vertical and horizontal ducts. The 
fresh air can be taken from the outdoors or from crawl or 
attic spaces that freely communicate with the outdoors. 
Attic or crawl spaces cannot be closed and must be 
properly ventilated to the outside. 
Ductwork must be of the same cross-sectional area as 
the free area of the opening to which they connect. The 
minimum dimension of rectangular air ducts cannot be less 
than three inches. 
The size of each of the two openings is determined by the 
method in which the air is to be provided. Refer to Table 
4 to calculate the minimum free area for each opening. 
Figures 6, 7, 8A and 8B are typical examples of each 
method. 
Louvers and Grilles                                                     
In calculating free area for ventilation and combustion 
air supply openings, consideration must be given to the 
blocking effect of protection louvers, grilles, and screens. 
These devices can reduce airflow, which in turn may 
require larger openings to achieve the required minimum 
free area. Screens must not be smaller than 1/4” mesh. If 
the free area through a particular design of louver or grille 
is known, it should be used in calculating the specified 
free area of the opening. If the design and free area are 
not known, it can be assumed that most wood louvers will 
allow 20 - 25% of free area while metal louvers and grilles 
will allow 60 - 75% of free area. 
Louvers and grilles must be locked open or interconnected 
with the equipment so that they are opened automatically 
during equipment operation. 
Keep louvers and grilles clean and free of debris or other 
obstructions.
TABLE 4
Minimum Free Area of Permanent Openings for 
Ventilation and Combustion Air Supply - All Air from 
Outdoors Only.
Based on total BTUH input rating for all utilizing 
equipment within the confi ned space.
Opening Source
Minimum Free Area 
Per Opening (sq. in.)
Reference Drawing
*Direct to outdoors
1 sq. in, per 4000 BTUH
Figure 6
Vertical Ducts
1 sq. in, per 4000 BTUH
Figure 7
Horizontal Ducts
1 sq. in, per 2000 BTUH
Figure 8A
Single Opening
1 sq. in, per 3000 BTUH
Figure 8B
Example: A water heater with an input rating of 50,000 BTUH using 
horizontal ducts would require each opening to have a minimum free 
area of 25 square inches.
Minimum free area = 50,000 BTUH x 1 sq. in. / 2000 BTUH = 25 sq. in.
*
  These openings connect directly with the outdoors through 
a ventilated attic, a ventilated crawl space, or through an 
outside wall.
Consult the local codes of your area for specific ventilation 
and combustion air requirements.
 
Confined
Space
Permanent
Openings
1 Square 
inch/1000
BTUH
(min. 100
sq. in.)