  Ductwork is the same cross-sectional area as the 
openings.
Vent Pipe System
Check for proper drafting at the water heater draft hood. 
Refer to the “Checking the Draft” section of this manual for 
the test procedure. If the procedure shows insufficient draft 
is present, please check the following.
  Draft hood properly installed.
  Vent connectors securely fastened with screws and 
supported properly to maintain six inch clearance.
  Vent connector made of approved material and sized 
correctly.
  Vent pipe system installed according to all local and 
state codes or, in the absence of local and state codes, 
the “National Fuel Gas Code”, ANSI Z223.1(NFPA 
54)-current edition.
  Flue baffle properly positioned in the flue tube.
  Check the vent system for restrictions/obstructions 
and check the vent termination height.  Refer to the 
“Combustion Air and Ventilation” section of this water 
heater manual for specific requirements.
□ 
Recheck for sufficient combustion air supply.
Water System Piping
  Temperature and pressure relief valve properly installed 
with a discharge line run to an open drain and protected 
from freezing.
  All piping properly installed and free of leaks.
  Heater completely filled with water.
  Closed system pressure build-up devices installed.
  Mixing valve (when applicable) installed per 
manufacturer’s instructions (See Water Temperature 
Regulation section).
Gas Supply and Piping
  Gas type is the same as that listed on the water heater 
rating plate.
  Gas line equipped with shut-off valve, union, and  drip 
leg.
  Use pipe joint compound or teflon tape marked as being 
resistant to the action of petroleum gases.
  Adequate pipe size and approved pipe material.
  An approved noncorrosive leak detection solution used 
to check all connections and fittings for possible gas 
leaks. Correct any leak found.
Electrical Supply
  Water heater to be located as close as possible to a 
120
VAC
 
outlet (extension cord is not allowed).
  Electrical supply installed according to all local and 
state codes or, in the absence of local and state codes, 
the “National Electrical Code”, ANSI/NFPS 70 current 
edition.
IMPORTANT INFORMATION ABOUT THIS WATER HEATER
This gas water heater was manufactured to voluntary safety standards to reduce the likelihood of a flammable vapor 
ignition incident. The new technology used in meeting these standards makes this product more sensitive to installation 
errors. Please review the following checklist and make any required installation upgrades or changes.  
Questions? Contact Residential Technical Assistance by referencing the phone number on the front of the Installation 
Instructions and Use & Care Guide.
Installation Checklist                                                  
Water Heater Location
Water heater location is important and can affect system 
performance. Please check the following:
  Installation area free of corrosive elements and 
flammable materials.
  Centrally located with the water piping system (For new 
installations). Located as close to the gas piping, vent 
pipe system and 120VAC outlet as possible.
  Located indoors and in a vertical position. Protected 
from freezing temperatures.
  Proper clearances from combustible surfaces 
maintained and not installed directly on a carpeted floor.
  Provisions made to protect the area from water damage. 
Metal drain pan installed and piped to an adequate 
drain.
  Sufficient room to service the water heater. See 
Clearances and Accessibility section of this manual.
  Water heater not located near an air moving device.
  Is the installed environment dirty (excessive amounts 
of lint, dirt, dust, etc.)?  If so, the air intake chamber 
louvers located on the side of the water heater 
will need to be cleaned periodically.  Refer to the 
maintenance section of your water heater’s manual 
for information on cleaning the “Air Intake Chamber 
Louvers”. 
Combustion Air Supply and Ventilation
Check for sufficient combustion air supply.  Insufficient air 
for the combustion of gas will result in a inferior burner 
flame “yellow-lazy”, thereby allowing smoking and carbon 
formation (sooting) to build up in the combustion chamber.
Is the water heater installed in a closet or other small, 
enclosed space? If so:
  Are there openings for make-up air to enter and exit 
the room/area? 
□ 
Are the openings of sufficient size?  Remember, if 
there are other gas-fired or air-consuming appliances 
in the same room, you need more make-up air.  Refer 
to the Location Requirements section of this water 
heater manual for specific requirements.
Fresh air not taken from areas that contain negative 
pressure producing devices such as exhaust fans, dryers, 
fireplaces, etc.
   Is there a furnace/air handler in the same room space 
as the water heater?  If so, has a return air duct system 
been attached that exits the room? If so, check for 
leaks on the air duct system. If no air duct system is 
present, correct immediately by contacting a local 
Heating, Ventilation, Air-Conditioning & Refrigeration 
(HVAC-R) authorized service provider. 
  Fresh air supply free of corrosive elements and 
flammable vapors.