40 • Chapter 3 Connecting Hardware 
 
DMC-3425 
to the ground, GND, of the interconnect and connect the GND of the interconnect to the GND of the 
amplifier.   
37 - 40
Pin Cable
ACMD
AMPEN
GND
ICM-1460
+5V
+12V
SERVO
MOTOR
AMPLIFIER
7407 Open Collector
Buffer.  The Enable signal
can be inverted by using
a 7406.
Analog Switch
Connection to +5V or +12V made through
jumper location JP1.  Removing the jumper
allows the user to connect their own supply to
the desired voltage level (Up to24V).
DMC-3425
 
 
Figure 3.1 - Connecting AEN to the motor amplifier 
TTL Inputs 
As previously mentioned, the DMC-3425 has 3 uncommitted TTL level inputs while the DMC-3415 
has 7 uncommitted TTL level inputs.  The command @IN, TI and TZ will read the state of the inputs.  
For more information on these commands refer to the Command Reference.   
The reset input is also a TTL level, non-isolated signal and is used to locally reset the DMC-3425 
without resetting the PC.   
Analog Inputs 
The DMC-3425 has 2 analog inputs configured for the range between –10V and +10V.  The inputs are 
decoded by a 12-bit ADC giving a voltage resolution of approximately .005V.  The impedance of these 
inputs is 10Kohms.  The analog inputs may be read using the @AN[n] function, where n is the number 
of the analog input to be read.