Goodman Mfg GSH13 Manual De Usuario

Descargar
Página de 8
4
www.goodmanmfg.com
SS-GSH13
P
roduct
 S
PecificationS
aHRi R
aTinGS
Outdoor
Unit
Indoor
Unit
Cooling Capacity¹
SEER²
EER³
TVA Ratings⁴
Heating Capacity¹
CFM
AHRI #
Total
Sens.
Total
Sens.
High
HSPF⁵
Low
GSH130484A*
AR*F486016B*
45,000 33,800 13.0
11.0 41,500 31,800 43,000
8.2
27,000 1,600 1492572
GSH130601A*
AR*F486016B*
55,500 41,000 13.0
11.0 51,500 37,000 55,500
8.5
35,000 1,800 1492576
GSH130603A*
AR*F486016B*
55,500 41,000 13.0
11.0 51,500 37,000 55,500
8.5
35,000 1,800 1492581
GSH130604A*
AR*F486016B*
55,500 41,000 13.0
11.0 51,500 37,000 55,500
8.5
35,000 1,800 1492585
GSH130241(B,C)*
AR*F182416B*+TXV
23,000 17,800 13.0
11.0 21,400 15,800 21,400
7.7
11,800
860
4675037
GSH130301(B,C)*
AR*F363616B*
27,800 20,200 13.0
11.0 25,800 19,300 25,400
7.7
15,300 1,020 4692016
GSH130181(B,C)*
AR*F182416B*
17,600 13,100 13.0
11.0 16,300 11,800 16,800
7.7
8,900
625
4675036
GSH130361(B,C)*
AR*F374316B*
33,600 26,200 13.0
11.0 31,000 23,400 31,400
7.7
18,200 1,260 4692017
GSH130604AC
AR*F486016B*
55,500 41,500 13.0
11.0 51,500 37,000 55,500
8.5
35,000 1,800 4982919
GSH130481B*
AR*F486016B*
45,000 33,800 13.0
11.0 41,500 31,800 43,000
8.2
27,000 1,600 5528480
GSH130421B*
AR*F364216B*
40,000 29,800 13.0
11.0 37,200 28,200 39,000
8.0
23,000 1,250 5528479
GSH130363A*
AR*F374316B*
33,600 26,200 13.0
11.0 31,000 23,400 31,400
7.7
18,200 1,260 5528484
GSH130483B*
AR*F486016B*
45,000 33,800 13.0
11.0 41,500 31,800 43,000
8.2
27,000 1,600 5528481
GSH130484AD
AR*F486016B*
45,000 33,200 13.0
11.0 41,500 31,800 43,000
8.2
27,000 1,600 5528482
¹   BTU/h
²    Seasonal Energy Efficiency Ratio; Certified per AHRI 210/240 @ 80°F/ 67°F/ 95°F
³    Energy Efficiency Ratio @ 80°F/ 67°F/ 95°F
⁴    TVA Rating: BTU/h @ 75°F/ 63°F - 95°F
⁵    HSPF = Heating Seasonal Performance Factor
Notes
•  Always check the S&R plate for electrical data on the unit being installed.
•  When matching outdoor unit to indoor unit, use the piston supplied with outdoor unit or that specified on the piston kit chart supplied with the indoor unit.
•  EEP - Order from Service Dept. Part No. B13707-38 or new Solid State Board B13707-35S. Part No. B13707-38 is not in-
terchangeable with B13707-35S. The Goodman Gas Furnace contains the EEP cooling time delay