SECTION 3: I
NSTALLATION
23 of 62
3.5 Pump Requirements
The pump is powered directly from the Variable
Frequency Drive (VFD). The VFD will be energized 
via an output from the relay board switched through a 
designated relay.
3.6 Variable Frequency Drive Requirements
The VFD must be powered separately from the 
control enclosure. The 230 V drive power supply 
must be 230 V, 50-60 Hz, 1 Ø. The 120V drive power 
supply must be 120 V, 50-60 Hz, 1 Ø. The 480 drive 
power supply must be 480 V, 50-60 Hz, 3 Ø. See 
Page 19, Section 2.7 for additional details. The VFD 
on/off switching is done by an output on the relay 
board. The 0-10 V signal from the ULTRAVAC™ 
controller enclosure wired into VFD input relays 5 and 
2 (
14will dictate the speed of the pump. The VFD 
output supply to the pump is 230 V 3 Ø 0-60 Hz for 
115 V and 230 V models and is 480 V, 3 Ø, 0-60 Hz 
for 480 V models. The frequency of the output supply 
signal to the pump will be varied based on the 0-10 V 
signal from the control enclosure. See 
tion 3.2 for additional installation requirements.
FIGURE 10: Variable Frequency Drive Mounting
(Standard enclosures only, NEMA 4 enclosure 
mounting varies by model)
 10" (25.4 cm)
14 .75"
(37.5 cm)