3.7 Indoor Sensor Placement
The sensor measures the air temperature in the 
building. It is important that the sensor is located in 
an area within the heated zone at occupant level. For 
the most accurate results, sensors should be 
mounted on an inside wall, away from any air vents 
or other sources of heat and cold. In order to avoid 
short system cycles and inaccurate temperature 
readings, do not mount sensors under the first 
section of radiant tube (first 10' (3 m) section of tube 
after the burner), in direct sunlight or in the path of 
other sources of radiant heat. The sensors are suit-
able for direct surface mounting or 4" (10.2 cm) x 
2.13" (5.4 cm) junction box mounting.
FIGURE 11: Indoor Sensor Mounting
3.7.1 Indoor Sensor Mounting
Remove the cover of the sensor by the two 1/16" 
allen screws, located in the lower corners of the 
cover. To gain access to the top mounting hole, 
remove the plug-in LCD display. To remove the LCD 
display, grasp the green plug-in board at the lower 
corners and gently pull the board away from the   
sensor back plate. 
removing the plug-in LCD display from its socket, 
secure the sensor to the wall or junction box using 
the screws provided. Replace the plug-in LCD dis-
play and secure the cover with the two 1/16" allen 
screws.
Wiring from 32 V terminals on the controller to 
sensor power terminals "+" and "-" is polarity 
sensitive. Reversing polarity may cause sensor 
or control board damage. Refer to 
3.8 Outdoor Sensor Placement
The outdoor sensor measures air temperature out-
side the building. It is important that the sensor is 
located on the outside of the building on the north 
facing wall. Failure to mount the sensor on the north 
facing wall will result in artificially high temperature 
readings. If possible, locate the sensor high under an 
eve to prevent incorrect readings from direct sunlight 
and damage due to the elements.
FIGURE 12: Outdoor Sensor Placement
Mount the outside sensor with the sensor module 
facing down to prevent accumulation of dirt or water.
3.9 Outside Air Supply
If an outside air blower is to be used, 
Figure 13 for external wiring diagrams. See Page 22, 
Section 3.4
 fo
r current load.
SEN
SET
O/R
-
+
Mounting
Hole
Plug-in LCD
Display
(grasp here
to unplug)
Mounting
Hole
Setback
Override
Button
Setpoint
Adjustment
Slide bar
North
Outside
Sensor
Sensor
Module
facing down