Greenheck Fan Model SFD Manual De Usuario

Descargar
Página de 8
Motor and Drive Installation Instructions
Model SWB units are shipped from stock without motors or drives .
1 . Adjust motor pulley to its closed position for 
maximum fan speed or increments of 1/2 turn 
open (maximum of 5 turns open) for reduced fan 
speed . Tighten set screw on flat area only .
4 . Install shaft pulley to fan shaft .
5 . Install drive belt(s) . Belts should not be forced 
over pulleys . Align motor and shaft pulleys with a 
straight edge . Tighten all set screws .
6 . Adjust belt tension .  
See page 6 for belt tensioning instructions .
2 . Install motor pulley to the motor shaft and install 
motor to the motor plate . Pre-punched holes are 
provided for most common motor frame sizes .
3 . If supplied, install taperlock bushing into  
shaft pulley .
2
Centrifugal Utility Fans
®