EcoBreeze System Installation
18
6. Locate the insulation strips packed in the ship-loose kit.
7. Remove the backing from the insulation and apply the insulation around the air transition 
ducts.
8. Open the damper on the supply air transition.
Water supply connection
N
OTE
There are two water supply inlets on the EcoBreeze Frame. Use separate sources if 
possible to provide a redundant water supply.
 
Sand filtration connections are provided if further filtration of the water supply is required. Sand 
filtration systems can be acquired from a third-party vendor.
NOTICE
DAMAGE TO EQUIPMENT
Install adequate freeze protection (not supplied) on all external water piping.
Freeze protection (which may consist of any combination of insulation and electric 
heat-tracing) must be correctly applied based on local climatic conditions and best 
practices. 
Failure to follow these instructions can result in equipment damage.