Regency P33-3 Zero Clearance Direct Vent Gas Fireplace
INSTALLATION
Diagram 3
HORIZONTAL INSTALLATIONS
Diagram 1
 b)  Horizontal runs of vent must be sup-
ported every three feet. Wall straps are 
available for this  purpose.
5)  Mark the wall for a 10" x 10"  square hole. 
The center of the square hole should line 
up with the centerline of the horizontal pipe. 
Cut and frame the 10 inch square hole in 
the exterior wall where the vent will be 
terminated. If the wall being penetrated is 
constructed of non-combustible material, 
i.e. masonry block or concrete, a 7"(178mm) 
diameter (7-1/2"(191mm) dia. for fl ex) hole 
is acceptable. 
Note:
 a)  The horizontal run of vent must be level, 
or have a 1/4 inch rise for every 1 foot 
of run towards the termination. Never 
allow the vent to run downward. This 
could cause high temperatures and 
may present the possibility of a fi re.
 
b)  The location of the horizontal vent termi-
nation on an exterior wall must meet all 
local and national building codes, and 
must not be blocked or obstructed.  For 
External Vent Terminal Locations, see 
diagram on page 9.
 
c)  Snorkel Terminations:
 
 
For installations requiring a vertical rise 
on the exterior of the building, 14-inch 
and 36-inch tall Snorkel Terminations 
and the Riser Vent  as shown in Dia. 2 & 
2a are available. Follow the same instal-
lation procedures as used for standard 
Horizontal Termination. NEVER install 
the snorkel upside down.
*As specifi ed in CGA B149 Installation Code. 
Local codes or regulations may require differ-
ent clearances.
Diagram 2
 
 
Below Grade Snorkel Installation
 
 
If the Snorkel Termination must be 
installed below grade, i.e. basement 
application, proper drainage must be 
provided to prevent water from enter-
ing the Snorkel Termination. Refer to 
Dura-Vent Installation instructions for 
details. Do not attempt to enclose the 
Snorkel within the wall, or any other type 
of enclosure.
6)  The arrow on the vent cap should 
be pointing up. Insure that the 1-1/2" 
clearances to combustible materials are 
maintained (Dia. 3). Install the termination 
cap.  AstroCap
TM
 or Dura-Vent Horizontal 
Termination Cap may be used.
Diagram 2a
Install the vent system according to the 
manufacturer's instructions included with the 
components.
1)  Set the unit in its desired location. Check 
to determine if wall studs or roof rafters 
are in the way when the venting system is 
attached. If this is the case, you may want 
to adjust the location of the unit. Rough in 
the gas preferably on the right side of the 
unit and the electrical (junction block is on 
the left side) on the left.
2)  Direct Vent pipe and fi ttings are designed 
with special twist-lock connections to con-
nect the venting system to the appliance 
fl ue outlet. A twist-lock appliance adaptor 
is an available option that must be used in 
conjunction with the Simpson Dura-Vent 
Direct Vent GS system. 
3)  Put a bead of silicone inside the outer sec-
tion of the adapter and a bead of Stove 
Mate on the inner collar. Slip the adapter 
over the existing inner and outer fl ue collar 
and fasten to the outer collar only with the 
3 supplied screws (drilling pilot holes will 
make this easier). Level the fi replace and 
fasten it to the framing using nails or screws 
through the nailing strips.
4)  Assemble the desired combination of pipe 
and elbows to the appliance adaptor and 
twist-lock for a solid connection.
Note:
 
a)    Twist-lock procedure: Four indentations, 
located on  the female ends of pipes and 
fi ttings, are designed to  slide straight 
onto the male ends of adjacent pipes 
and fi ttings, by orienting the four pipe 
indentations so they match and slide 
in to the four entry slots on the male 
ends, Dia. 1. Push the pipe sections 
completely  together, then twist-lock 
one section clockwise approximately 
one-quarter turn, until the two sections 
are fully locked. The female locking lugs 
will not be visible from the outside, on 
the Black Pipe or fi ttings. They may be 
located by examining the inside of the 
female ends.   
Note:   Apply sealant "Mill-Pac" to inner pipe 
and high temperature silicone seal-
ant to outer pipe on every twist-lock 
joint.
 
The four wood screws provided should 
be replaced with appropriate fasteners for 
stucco, brick, concrete, or other types of 
sidings.
Note:  If installing termination on a siding 
covered wall, a vinyl siding standoff or 
furring strips must be used to ensure 
that the termination is not recessed 
into the siding.
 
7)  Before connecting the horizontal run of vent 
pipe to the vent termination, slide the Wall 
Thimble (Part # 620-926) over the vent 
pipe.
8)  Slide the appliance and vent assembly to-
wards the wall carefully inserting the vent