Regency P33-3 Zero Clearance Direct Vent Gas Fireplace
GAS PIPE PRESSURE 
TESTING
The appliance must be isolated from the gas 
supply piping system by closing its individual 
manual shut-off valve during any pressure 
testing of the gas supply piping system at 
test pressures equal to or less than 1/2 psig. 
(3.45 kPa).  Disconnect piping from valve at 
pressures over 1/2 psig.
The manifold pressure is controlled by a regu-
lator built into the gas control, and should be 
checked at the pressure test point.
Note: To properly check gas pressure, both 
inlet and manifold pressures should 
be checked using the valve pressure 
ports on the valve.
1)  Make sure the valve is in the "OFF" posi-
tion.
2)  Loosen the "IN" and/or "OUT" pressure 
tap(s), turning counterclockwise with a 1/8" 
wide fl at screwdriver.
3)  Attach manometer to "IN" and/or "OUT" 
pressure tap(s) using a 5/16" ID hose.
4)  Light the pilot and turn the valve to "ON" 
position.
5)  The pressure check should be carried out 
with the unit burning and the setting should 
be within the limits specifi ed on the safety 
label.
6) When fi 
nished reading manometer, turn 
off the gas valve, disconnect the hose and 
tighten the screw (clockwise) with a 1/8" 
fl at  screwdriver.  Note: Screw should be 
snug, but do not over tighten.
INSTALLATION
Incorrect fl ame pattern will have small, prob-
ably yellow fl ames, not coming into proper 
contact with the rear burner or thermopile 
or thermocouple. 
 
HIGH ELEVATION
This unit is approved in Canada for altitude 
to 4500 ft. (CAN/CGA-2.17-M91). For Natural 
Gas installations above 4500 ft. follow current 
CAN/CGA-B149.1.
S.I.T. VALVE DESCRIPTION
1)  Gas cock knob
2) Manual 
high/low 
adjustment
3) Pilot 
Adjustment
4)  Thermocouple Connection - option
5)  Outlet Pressure Tap
6) Inlet 
Pressure 
Tap
7) Pilot 
Outlet
8)  Main Gas Outlet
9) Alternative 
TC 
Connection 
Point
PILOT ADJUSTMENT
Periodically check the pilot fl ames. Correct 
fl ame pattern has three strong blue fl ames: 
1 fl owing around the thermopile, 1 around 
the thermocouple and 1 fl owing across the 
burner (it does not have to be touching the 
burner).
Note: 
If you have an incorrect fl ame pat-
tern, contact your Regency dealer for further 
instructions.
P33-NG3 System Data 
Conversion Kit# 431-969
For 0 to 2000 feet altitude
Burner Inlet Orifi ce Sizes: 
#44 
                 
Max. Input Rating 
22,500 Btu/h
Min. Input Rating 
12,500 Btu/h
For 2000 to 4500 feet altitude
Burner Inlet Orifi ce Sizes: 
#45 
                 
Max. Input Rating 
21,000 Btu/h
Min. Input Rating 
10,500 Btu/h
Supply Pressure min.5.0" 
w.c.
Manifold Pressure  
 (High)
  
3.8"+/- 0.2" w.c.
P33-LG3 System Data 
For 0 to 4500 feet altitude
Burner Inlet Orifi ce Sizes: 
#54
 
 
                  
Max. Input Rating  21,500 
Btu/h 
Min. Input Rating 
10,500 Btu/h 
 
Supply Pressure min.12.0" 
w.c.
 
 
 
Manifold Pressure  
 (High)
 11"+/- 
0.2"w.c.