Minimum Wall and Ceiling Clearances (Figure 4)
Sidewall Clearances: The clearance from the inside of the fireplace 
to any combustible wall should not be less than 2".
Fireplace Side and Back Clearances: The fireplace outer casing 
sides and back have zero clearance to combustibles.
Ceiling Clearances: The ceiling height should not be less than 36" 
from the top of the hood.
Mantel Clearances: Vent free fireplace models must use the hood 
supplied with the fireplace. If a combustible mantel is installed, 
it must meet the clearance requirements detailed above.
Figure 4
2”
36”
COMBUSTIBLES
ALLOWED
MANTEL
HOOD
2”
7”
4”
9 3/4”
4 1/4”
6”
12 ½”
8”
15 1/4”
18”
10”
12”
Figure 5
Mantel Clearances (Figure 5)
Checking Manifold Pressure
VFP(32,36)FP(30,31)LN  (Natural  gas)  will  have  a  manifold 
pressure of approximately 3.5" w.c. (.871kPa) for maximum input or  
1.7" w.c. (.423kPa) for minimum input at the pressure regulator outlet 
with the inlet pressure to the pressure regulator from a minimum 
of 4.5" w.c. (1.120kPa) for the purpose of input adjustment to a 
maximum  of  10.5"  w.c.  (2.614kPa).  VFP(32,36)FP(20,21)LN 
(Natural gas) will have a manifold pressure of approximately 6.0" 
w.c. (1.49kPa) at the pressure regulator outlet with the inlet pressure 
to the pressure regulator from a minimum of 7.0" w.c. (1.74kPa) 
for the purpose of input adjustment to a maximum of 10.5" w.c. 
(2.615kPa). VFP(32,36)FP(30,31)LP (Propane gas) will have a 
manifold pressure approximately 10.0"w.c. (2.49kPa) for maximum 
input or 4.9"w.c. (1.220kPa) for minimum input at the pressure 
regulator outlet with the inlet pressure to the pressure regulator 
from a minimum of 11.0"w.c. (2.739kPa) for the purpose of input 
adjustment to a maximum of 13.0"w.c. (3.237kPa). 
VFP(32,36)FP(20,21)LP  (Propane  gas)  will  have  a  manifold 
pressure  approximately  10.0"w.c.  (2.49kPa)  at  the  pressure 
regulator outlet with the inlet pressure to the pressure regulator 
from a minimum of 11.0"w.c. (2.739kPa) for the purpose of input 
adjustment to a maximum of 13.0"w.c. (3.237kPa). 
A test gage connection is located downstream of the gas appliance 
pressure regulator for measuring gas pressure. The connection is 
a 1/8 inch (3mm) N.P.T. plugged tapping.
VFP(32,36)FP(30,31) Millivolt Control
The valve regulator controls the burner pressure which should be 
checked at the pressure test point. Turn captured screw counter 
clockwise 2 or 3 turns and then place tubing to pressure gauge 
over test point (Use test point “A” closest to control knob). After 
taking pressure reading, be sure and turn captured screw clockwise 
firmly to re-seal. Do not over torque. Check for gas leaks.
GAS SUPPLY (continued)
CLEARANCES