Check all local codes for requirements, especially for the size and 
type of gas supply line required.
Recommended Gas Pipe Diameter
Pipe Length
Schedule 40 Pipe
Inside Diameter
Tubing, Type L 
Outside Diameter
Nat.
L.P.
Nat.
L.P.
0-10 feet
0-3 meters
1/2”
12.7mm
3/8”
9.5mm
1/2”
12.7mm
3/8”
9.5mm
10-40 feet
4-12 meters
1/2”
12.7mm
1/2”
12.7mm
5/8”
15.9mm
1/2”
12.7mm
40-100 feet
13-30 meters
1/2”
12.7mm
1/2”
12.7mm
3/4”
19mm
1/2”
12.7mm
100-150 feet
31-46 meters
3/4”
19mm
1/2”
12.7mm
7/8”
22.2mm
3/4”
19mm
Note: Never use plastic pipe. Check to confirm whether your local 
codes allow copper tubing or galvanized.
Note:  Since  some  municipalities  have  additional  local  codes, 
it is always best to consult your local authority and installation 
code.
Installing a New Main Gas Cock 
Each appliance should have its own manual gas cock.
A  manual  main  gas  cock  should  be  located  in  the  vicinity  of 
the unit. Where none exists, or where its size or location is not 
adequate, contact your local authorized installer for installation 
or relocation.
Compounds used on threaded joints of gas piping shall be resistant 
to the action of liquefied petroleum gases. The gas lines must be 
checked for leaks by the installer. This should be done with a soap 
solution watching for bubbles on all exposed connections, and if 
unexposed, a pressure test should be made. 
Never use an exposed flame to check for leaks. Appliance must 
be disconnected from piping at inlet of control valve and pipe 
capped or plugged for pressure test. Never pressure test with 
appliance connected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas 
line upstream of the gas control to aid in servicing. It is required 
by the National Fuel Gas Code that a drip line be installed near 
the gas inlet. This should consist of a vertical length of pipe tee 
connected into the gas line that is capped on the bottom in which 
condensation and foreign particles may collect.
The use of the following gas connectors is recommended:
—  ANS  Z21.24  Appliance  Connectors  of  Corrugated  Metal 
Tubing and Fittings
—  ANS Z21.45 Assembled Flexible Appliance Connectors of 
Other Than All-Metal Construction
The above connectors may be used if acceptable by the authority 
having  jurisdiction  The  state  of  Massachusetts  requires  that  a 
flexible appliance connector cannot exceed three feet in length.
Figure 3
GAS SUPPLY