 H35 Direct Vent Freestanding Gas Stove
Review the following sequence of instructions 
which are typical of most installations. The se-
quence may vary depending on wall thickness. 
See "Exterior Vent Terminal Locations" to 
"Venting Arrangements" section for vent 
location and clearance dimensions, and the 
"Vent Restrictor Position" section to set the  
Vent Restrictor to the correct position.
1)  Set the unit in its desired location. Check 
to determine if wall studs will be in the way 
of the venting system, adjust location until 
all clearances are met and there are no 
obstructions.
Note:  A 1-1/2"(38mm) clearance around the 
outer pipe must be maintained except 
that only a 1" (25mm) clearance is 
needed at the termination end. 
IMPORTANT:
Do not locate termination hood 
where excessive snow or ice 
buildup may occur. Be sure to check 
vent termination area after snow 
falls, and clear to prevent accidental 
blockage of venting system. When 
using snow blowers, make sure 
snow is not directed towards vent 
termination area.
 
b)  Install wall thimbles on both interior 
and exterior wall with 4 wood screws 
(#8 x 1") per thimble.
 
c)  Attach the 2 piece adjustable pipe sec-
tion to the vent terminal and slide into 
position from the exterior. The larger 
diameter end of the adjustable pipe 
goes to the vent terminal.
 
d)  Install the 90
o
 elbow onto the adjust-
able pipe  to determine the vertical 
centerline. 
 
 
Note: if the centerline cannot be met, 
the adjustable sections will have to 
be cut.
 
e)  Cut the 4 ft. section of rigid pipe to 
length. Attach the  45
o
 elbow to the rigid 
pipe, and ensure that the pipe length 
when cut  (with the 45
o
 elbow) will seat 
onto both the starter collar and the 90
o
 
elbow.  Crimped section of rigid pipe 
seats into the 90
o
 elbow. Only cut 
the uncrimped side of pipe. 
 
Dismantle all pipe sections including vent 
terminal.
2) Assemble 
trial fi t to determine the vertical 
center-line for the vent termination.
 
a)  Cut a 9-1/2" x 9-1/2" (241mm x 241 
mm) square hole on both the interior 
and exterior wall.
INSTALLATION
DV STOVE HORIZONTAL VENT KIT
DV 2 ft.  Stove Vent Kit (Part # 946-116)  and DV 4 ft. Stove Vent Kit (Part #946-216) includes all the parts 
needed to install the H35 Direct Vent unit with minimum horizontal and vertical vent dimensions. 
For installations that require longer vertical and/or horizontal vents use the Dura-Vent system as 
shown in the "Dura-Vent Termination Kit" and "Dura-Vent Venting Components" sections.
       Qty.  
Description
1)   
1   
Rigid Pipe Section (Kit # 946-116: 2 ft. (1.2m) length,
 
 
   
Kit # 946-216: 4 ft. (1.2m) length), 6-1/2" (165mm) 
    
  inside 
diameter 
2)   
1   
Flex Liner, compressed aluminium 2 ply liner, 4" (102mm) 
    
  inside 
diameter
3)   4  
Spring 
Spacers
4)   1  
90 
deg. 
Elbow
5)   
1   
Adjustable pipe section 13-1/2" to 24" (343mm x 610mm), 2 
pcs.
6)   1  
Thimble 
Cover
7)   1  
Wall 
Thimble 
(2 
pcs.)
8)   1  
Adapter 
9)   1  
AstroCap Termination Cap
10)  
2   
Trim Collars
11)  
1   
Tube of Mill-Pac, high temperature sealant
12)   12   
Screws, #8 x 1/2" Self tapping, Stainless Steel
13)   14   
Screws, #8 x 1/2" Self tapping, Black
14)  
4   
Screws #8 x 1-1/2" Drill Point, Black
15)  
4   
Screws #8 x 1-1/2" Drill Point, Stainless Steel
16)  
8   
Wood screws #8 x 1"
Required but not included in above Kit: 
45
o
 Elbow (Part #: 946-214)
Note: 
a)  Liner sections should be con-
tinuous without any joints or 
seams.
b)  This is an approved system, 
therefore components in this 
system must not be substituted 
for any other manufacturer's 
products.
DV STOVE HORIZONTAL VENT KIT (#946-116 & #946-216) INSTALLATION