Carrier 50VQP084-300 Manual De Usuario
3
Table 1 — 50VQP Unit Physical Data
LEGEND
NOTES:
1. All units have grommet and spring compressor mountings, and
2.2 cm and 3.5 cm electrical knockouts.
2. Use the lowest maximum pressure rating when multiple options
are combined:
UNIT 50VQP
084
096
120
150
168
192
240
300
COMPRESSOR QUANTITY
Scroll (1)
Scroll (2)
Factory Charge HFC-410A (kg) per circuit
3.97
4.42
6.35
7.03
3.97
4.42
6.35
7.03
BLOWER MOTOR
Blower Motor Quantity
Blower Motor Quantity
1
Standard Motor (kW)
.75
1.12
1.49
2.24
1.49
2.24
3.73
3.73
Large Motor (kW)
1.12
1.49
2.24
3.73
2.24
3.73
5.60
5.60
BLOWER
No. of Blowers
No. of Blowers
1
2
Blower Wheel Size D x W (cm)
38.1 x 27.9
38.1 x
38.1
38.1 x 27.9
38.1 x
38.1
WATER CONNECTION SIZE
FPT (in.) [mm]
1-1/2 [38.1]
2 [50.8]
2-1/2
[63.5]
COAX VOLUME
Volume (liters)
Volume (liters)
8.28
9.37
13.11
18.29
24.08
27.98
CONDENSATE CONNECTION SIZE
FPT (in.) [mm]
FPT (in.) [mm]
1 [25.4]
AIR COIL DATA
Air Coil Dimensions H x W (cm)
Air Coil Dimensions H x W (cm)
91.4 x 121.9
91.4 x 121.9
Air Coil Total Face Area (sq m)
1.11
2.22
Air Coil Tube Size (cm)
3/8 [0.953]
Air Coil Fin Spacing (fins per cm)
5.5
4.72
5.5
4.72
Air Coil Number of Rows
2
3
4
2
3
4
MISCELLANEOUS DATA
Filter Standard Throwaway (qty) (cm)
Filter Standard Throwaway (qty) (cm)
(4) 45.74 x 63.5 x 2.5
(8) 45.74 x 63.5 x 2.5
Weight - Operating (kg)
399
422
435
725
755
769
Weight - Packaged (kg)
406
429
442
739
769
782
FPT — Female Pipe Thread
OPTION
MAXIMUM PRESSURE (kPa)
Base Unit
3100
Motorized Water Valve
2750
Internal Secondary Pump
999
T
Optional Discharge
Supply Air
Optional Discharge
Access
Panel
Panel
Access
Panel
Panel
Access
Panel
Panel
Access
Panel
Panel
Vibration
Pad
Pad
Control Box
Supply Air
Supply Water
Return
Water
Water
Balancing
Valve
Valve
Valves
Trap
Condensate
24 V Remote
Mtd. Stat
Mtd. Stat
Power
Supply
Supply
Disconnect
Switch or
Per Local Codes
Switch or
Per Local Codes
Condensate
Water In
Water Out
Unions
Fig. 1 — Typical 50VQP Unit Installation