C. Check remote control unit.
D. Check fuse on the indoor PCB Ass'y.
E. Check TIMER on the remote control unit.
• Timer is turned ON. Check to see 
if             is displayed on remote 
control.
YES
Cancel the timer mode.
ON
OK
OK
• Check fuse on indoor PCB Ass'y 
for continuity.                              (F)
• Check operation lamp to see 
if light is ON.
Light is OFF
• Measure resistance of primary and 
secondary winding of transformer.
                                                   (TR)
Indoor PCB Ass'y or switch Ass'y is 
defective.
OK
OK
• Measure resistance of indoor and/or 
fan motor winding.
                                       
(FM)
• Measure resistance of compressor        
motor winding.                       (CM)
OK
• Measure coil resistance of  power 
relay.
(PR)
Replace the fuse.
If fuse has been blown,
OK
• Try to run with another remote 
control unit.
First remote control unit is defective.
• Check for residue buildup on 
transmitter of remote control unit.
• Check for residue buildup on remote 
control receiver on front of indoor 
unit.
Clean transmitter.
Clean receiver.