PREPARATION FOR INSTALLATION
IMPORTANT: RetroAire Dual Motor PTACs are to be used 
with  metal  wallsleeves. The  sleeves  must  employ  front 
panels secured by screws that prevent contact with all parts 
with minor dimensions of openings not exceeding 1/2”. The 
final assembly must employ an indoor air discharge grill 
having dimensions not less than 26” x 4”, separating the top 
surface of the chassis from the top surface of the discharge 
grill  by  a  minimum  of  1”.  For  all  models,  the  outdoor 
openings must prevent contact of all moving parts by means 
of louvers or grills with minor dimension not exceeding 1”.
 
All  cord  connected  265  Volt  units  must  be  plugged  into 
receptacles within the unit subbase or chassis.
1. Remove the front of the existing room enclosure. This 
will expose the old chassis.
2. Disconnect the power supply. If a line cord and plug 
were used, remove it from the receptacle. If the chassis 
is hard wired, locate the circuit breaker, place it in the 
“OFF” position, and tag it, announcing work is being 
done. DO NOT TURN ON.
3. Loosen any tie down bolts or screws and remove the 
old chassis. 
IMPORTANT: Dispose of old chassis per present state 
and federal regulations.
4. Inspect the wall sleeve/cabinet for rust, holes, and dam-
age. Clean the wall sleeve of any dirt, repair any damage, 
and ensure proper drainage of condensate or rainwater 
to exterior of building.
5. Remove or repair old weather seals and note location 
for installation of any new seals.
6. Check the wall sleeve/cabinet to assure all drain holes 
are open and that (A) the unit is level left to right and (B) 
the back is pitched to the outside by 1/2” maximum.
7. Check the present voltage to verify the new chassis is a 
matching voltage and that the line cord and receptacle 
match.
8. Before installing the new chassis, inspect the outdoor 
louver for a  minimum free area of 70% and remove 
any obstructions. Any variation will restrict air flow over 
the condenser coil and cause serious  damage to the 
chassis. It will also void the warranty.
 
The correct condenser air baffles must be properly 
installed or performance will be impaired and/or the 
warranty will be voided!!
See individual unit installation instructions for more 
information.
!  
!  
WARNING
Moving parts can cause personal injury. Exercise 
all due caution when test running the chassis.
!  
!  
WARNING
ELECTRICAL WIRING
All wiring should be in accordance with the National Electric 
Code (NEC) and the local building codes.
1. Inspect the existing wiring for any deficiencies such as 
cut or frayed wires. Replace such wiring if found.
2.  Check  the  unit  rating  plate  for  circuit  ampacity  and 
breaker or fuse size. 
Use only HACR type breakers
Select the proper wire for the ampacity rating.
3. If plug and receptacle are used, check the compatibility. 
The chassis can be hard wired or direct connected as 
well. 
4. Each unit must have a separate branch ciruit protected 
by a fuse or breaker. Refer to the unit rating plate for the 
proper wire and breaker or fuse size. 
Use of extension 
cords is prohibited.
To avoid possible injury or death due to electrical 
shock, open the power supply disconnect switch 
and secure it in an open position during installation. 
On a plug and receptacle connection, keep the unit 
unplugged until installation is complete.
!  
!  
WARNING
The RetroAire Dual Motor PTAC must:
 Be connected to a properly grounded electrical 
supply with the proper voltage as stated on the 
rating plate.
 Use the proper maximum over current protection 
device stated on the rating plate.
The use of extension cords is prohibited.
Failure to follow these instructions can result in a fire, 
explosion or electrical shock causing property damage, 
personal injury or death.
!
  
!
  
DANGER