The Right Fit For Comfort
EVAP
 BLOCK OFF
Install 
1/2” x 1/2” 
Foam Tape
1. Take unit out of packaging. 
2. Slide unit into wall sleeve. If supply duct on cooling chassis does 
not line up with supply vent on room cabinet it is possible that 
factory installed angle brackets on the top and sides will have 
to be reversed. This will allow approximately 1” in or out of the 
wall sleeve (see figures A & B) below.
3. Slide unit out of wallsleeve.
4. Baffl e Installation -  Remove baffl es from kit bag supplied 
with unit. Install left and right side baffl es on the condenser 
coil in existing holes: 
• Choose the proper fi tting baffl es for your application. 
• Baffl es must come in contact with the outdoor louver.  
5. Apply one piece of 1/2” x 1/2” open cell polyfoam to top fl ange 
of evaporator block off (See illustration at left).
6. Apply 2” x 1 1/2” open cell foam strips around supply air 
duct to ensure that all the conditioned air is delivered into 
the  room.  Failure  to  do  so  results  in  recirculation  of  the 
conditioned air around the wall sleeve and through the unit 
causing the unit to short cycle and coils to freez, thus rais-
ing operating costs through improper heating and cooling 
(Figure C1).
7. 1” x 1” Open cell foam strips are provided to prevent outside air 
from entering around the chassis to the room from the sides 
and top of the cabinet. Install between wall sleeve and cooling 
chassis. It is imperative to have a solid air seal between wall 
sleeve and chassis. Failure to do so will result in air leakage 
*Refer to the charts on page 23 for electrical and 
optional electric heat specifi cations.
RC/RH 10 PERFORMANCE DATA*
Unit Size Cooling Btuh EERs Heat Pump Btuh COP Fresh Air CFM
9
9,500
10.0
8,500
2.8
40/35
12
11,900
10.0
11,400
2.9
40/35
15
14,700
9.2
13,800
2.8
40/35
18
16,900
9.1
N/A
N/A
40/35
INSTALLATION INSTRUCTIONS
RC/RH10 REPLACEMENT PTAC
• 1 Installation Manual
• 1 Top Baffl e
• 2 Sets of Lt.&Rt. Baffl es
• Screws 
RC/RH10 BAFFLE INSTALLATION KIT
• 1/2” x 1/2” Open Cell Foam Tape
• 1” x 1” Open Cell Foam Tape
• 2” x 1 1/2” Open Cell Foam Tape
• 1ea. 2-Position Connector & Pin Mate
• 14AWG Yellow Wire
HYDRONIC
 ONLY
Two sets of baffl es are provided in your kit to accommodate 
mounting brackets in either position A or B.
•  Make  sure  baffles  are 
directed  inward  toward 
the center of coil. 
•  Secure  baffl es  tightly  to 
the condenser coil using 
the screws provided. 
  (Figures A1,B1 & C1).
IMPORTANT:  The  correct 
condenser  air  baffl es  must 
be installed or performances 
may be impaired and/or the 
warranty will be voided. 
2” X 1 1/2” Supply Air 
Duct Foam Tape
CONDENSER SIDE
Baffl es Directed Inward 
Toward Coil
Figure C1
��������
�������
���
���������������
��������������
from  outdoor  to 
indoor  causing 
system problems 
i.e. coils freezing, 
short cycling, and 
constant running 
of unit. If install-
er  is  in  need  of 
more  foam  than 
supplied  in  kit, 
consult  factory 
(Figure D1). 
8. Once confi dent that all seals are the correct size and in the 
proper location, and the correct baffl es are attached to the con-
denser coil in the proper orientation, slide unit into fi nal position 
and tighten any tie down bolts or screws as necessary.
Hydronic Only: Remove the 2-position connector assembly 
from kit bag supplied with unit (this will have 2 yellow wires 
attached). Connect this 2-position connector to the 2-position 
connection located on the bottom of the control box panel. 
To Connect Aquastat: 
A. Remove the black jumper wire located on the bottom 
panel of the control box (this is also terminated with a 
2-position connector).
B. Cut the jumper wire in the middle and splice the aquastat 
to the jumper. 
C. Place the connecter back into original location. Refer 
to wire diagram on the unit for details.
9. Connect line cord. 
10. See Final Inspection and Startup on page 20.
Figure D1
Front View
Cooling Chassis
Wall Sleeve
1�x1� Foam Tape
Figure A1
Figure B1