Friedrich SH15L30-A Manual De Usuario

Descargar
Página de 20
6
RED DOT
RUN CAPACITOR
FAN
MOTOR
COMPRESSOR
FIGURE 7    RUN CAPACITOR HOOK–UP
CAPACITOR, RUN
A run capacitor is wired across the auxiliary and main 
winding of a single phase permanent split capacitor 
motor such as the compressor and fan motors.  A single 
capacitor can be used for each motor or a dual rated 
capacitor can be used for both.
The capacitor’s primary function is to reduce the 
line current while greatly improving the torque 
characteristics of a motor.  The capacitor also reduces 
the line current to the motor by improving the power 
factor of the load.  The line side of the capacitor is 
marked with a red dot and is wired to the line side of 
the circuit (see Figure 7.)
THERMOSTAT
A cross ambient 
thermostat is used to 
maintain the desired 
comfort level.  The 
thermostat reacts only to a 
change in temperature at the 
bulb location.  
Important to the 
successful operation 
of the unit is the position
of the sensing bulb in
relation to the evaporator
 (see Figure 8).
FIGURE 8  SENSING 
BULB LOCATION
CAPACITOR – TEST
1.  Remove the capacitor from the unit.
2.  Check for visual damage such as bulges, cracks, 
or leaks.
3.  For dual rated capacitors, apply an ohmmeter lead 
to the common (C) terminal and the other probe to 
the compressor (HERM) terminal.  A satisfactory 
capacitor will cause a defl ection on the pointer, 
then gradually move back to infi nity.
4.  Reverse the leads of the probe and momentarily 
touch the capacitor terminals.  The defl ection of the 
pointer should be two times that of the fi rst check 
if the capacitor is good.
5.  Repeat steps 3 and 4 to check the fan motor 
capacitor.
NOTE:  A shorted capacitor will indicate a low 
resistance and the pointer will move more to the 
“0” end of the scale and remain there as long as 
the probes are connected. An open capacitor 
will show no movement of the pointer when 
placed across the terminals of the capacitor. 
SYSTEM CONTROL SWITCH (Figure 6)
This switch is double pole, single throw. Check for 
continuity between terminals 2 and 3, and 5 and 6.
FIGURE 6  SWITCH, ON-OFF
RANGE:
Thermostat
(Part No. 618-225-02)
60° F ( ± 2° ) to 90° F( ± 4° )