Troubleshooting: Semi-Annual Preventive Maintenance
68
NetworkAIR IR Operation, Maintenance, and Troubleshooting
Airflow too high
• External static pressure may 
be too low.
• Check the evaporator coil pressure drop through 
the display interface. Pressure should match the 
recommended pressure drops indicated on the 
chart based on Module size. If the pressure drop is 
above the recommended settings, decrease the 
blower speed until the pressure drop matches the 
recommended setting. See “Calibrate airflow 
manually” on page 17.
Temperature control 
not precise enough
• Cooling and reheat settings 
are not close enough.
• Reheat PID loop is not 
properly tuned.
• SCR controller is not 
working.
• The mode of operation is 
turned off.
• Non-essential lockout has 
been activated by a user-
defined input with the 
equipment.
• Return air temperature is 
reading incorrectly.
• Check setpoints for cooling and heating as well as 
deadbands. 
• Tune the PID loop for accurate reheat operation.
• Confirm the operation of the SCR controller.
• Check to verify that the proper modes of 
operation, cooling, and reheat are activated. A 
Module must have specific options installed to 
allow all modes of operation to be active.
• Review event log to see if this alarm input has 
been activated.
• Return air is not coming from the common space 
and may be influenced by a close heat source or a 
discharge air duct affecting return air 
temperatures. Try to eliminate the hot or cold air 
stream or relocate the sensor for better room 
temperature readings.
Humidification 
control is not 
precise enough
• Check the setpoints for 
humidification and 
dehumidification.
• Humidifier may not be 
operating correctly.
• The mode of operation is 
turned off.
• Non-essential mode input 
has been activated by 
customer interface with 
equipment.
• The room is not properly 
sealed internally to maintain 
vapor pressure in the 
controlled space.
• Verify that the setpoints are not too far apart. 
Typical setpoint between humidification and 
dehumidification is 10%.
• Verify humidification operation. Ensure that there 
are no humidifier alarms that could impede the 
humidification process.
• Ensure that the proper modes of operation, 
humidification and dehumidification, are 
activated. A Module must have specific options 
installed to allow all modes of operation to be 
active.
• Review the event log to see if this alarm input has 
been activated.
• The room must have an adequate vapor barrier 
installed to maintain humidification and 
dehumidification setpoints. The vapor barrier is 
inadequate if humidity in the controlled space 
changes based on influences from the surrounding 
air outside the controlled space.
Problem
Possible Cause
Corrective Action