PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E240
LEGEND
566E240/524A-C240 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
6,000
8,000
10,000
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
80
TC
228.0
239.0
258.0
279.0
248.0
252.0
269.0
290.0
262.0
262.0
277.0
297.0
SHC
228.0
207.0
174.0
139.0
248.0
240.0
199.0
155.0
262.0
262.0
222.0
169.0
kW
17.60
18.00
18.70
19.40
18.30
18.40
19.10
19.80
18.80
18.80
19.30
20.10
85
TC
225.0
235.0
254.0
274.0
245.0
248.0
265.0
285.0
258.0
258.0
272.0
291.0
SHC
225.0
205.0
172.0
137.0
245.0
237.0
197.0
153.0
258.0
258.0
220.0
167.0
kW
18.40
18.70
19.40
20.10
19.10
19.20
19.80
20.60
19.60
19.60
20.10
20.80
95
TC
218.0
227.0
244.0
263.0
236.0
238.0
254.0
274.0
249.0
249.0
261.0
280.0
SHC
218.0
201.0
168.0
134.0
236.0
232.0
193.0
149.0
249.0
249.0
216.0
163.0
kW
20.00
20.30
21.00
21.70
20.70
20.70
21.30
22.10
21.10
21.10
21.60
22.40
100
TC
214.0
222.0
239.0
258.0
232.0
234.0
249.0
268.0
245.0
245.0
255.0
274.0
SHC
214.0
199.0
166.0
132.0
232.0
229.0
190.0
147.0
245.0
245.0
213.0
161.0
kW
20.90
21.10
21.70
22.50
21.50
21.50
22.10
22.90
22.00
22.00
22.40
23.10
105
TC
211.0
217.0
234.0
252.0
228.0
229.0
243.0
262.0
240.0
240.0
249.0
267.0
SHC
211.0
196.0
163.0
130.0
228.0
226.0
188.0
145.0
240.0
240.0
211.0
159.0
kW
21.70
22.00
22.60
23.30
22.40
22.40
22.90
23.70
22.80
22.80
23.20
23.90
115
TC
203.0
207.0
223.0
241.0
219.0
219.0
231.0
249.0
230.0
230.0
237.0
254.0
SHC
203.0
192.0
159.0
125.0
219.0
219.0
184.0
140.0
230.0
230.0
206.0
155.0
kW
23.50
23.70
24.30
25.00
24.10
24.10
24.60
25.40
24.60
24.60
24.90
25.60
566E240/524A-B240 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
6,000
8,000
10,000
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
80
TC
219.0
229.0
248.0
267.0
237.0
241.0
259.0
278.0
250.0
251.0
265.0
285.0
SHC
219.0
199.0
167.0
134.0
237.0
228.0
190.0
148.0
250.0
250.0
211.0
161.0
kW
17.30
17.70
18.30
19.00
17.90
18.10
18.70
19.40
18.40
18.40
18.90
19.60
85
TC
216.0
226.0
243.0
263.0
234.0
237.0
254.0
273.0
246.0
247.0
261.0
280.0
SHC
216.0
197.0
165.0
132.0
234.0
226.0
188.0
146.0
246.0
246.0
209.0
159.0
kW
18.10
18.40
19.00
19.70
18.70
18.80
19.40
20.10
19.10
19.10
19.70
20.40
95
TC
209.0
217.0
234.0
253.0
226.0
228.0
244.0
263.0
238.0
238.0
250.0
269.0
SHC
209.0
192.0
161.0
128.0
226.0
221.0
184.0
142.0
238.0
238.0
205.0
155.0
kW
19.70
20.00
20.60
21.30
20.30
20.40
20.90
21.70
20.70
20.70
21.20
21.90
100
TC
206.0
213.0
230.0
248.0
222.0
224.0
239.0
257.0
234.0
234.0
245.0
263.0
SHC
206.0
190.0
159.0
126.0
222.0
218.0
182.0
140.0
234.0
234.0
202.0
153.0
kW
20.60
20.80
21.40
22.10
21.10
21.20
21.70
22.50
21.50
21.50
22.00
22.70
105
TC
202.0
209.0
225.0
242.0
218.0
219.0
233.0
251.0
229.0
229.0
239.0
257.0
SHC
202.0
188.0
157.0
124.0
218.0
215.0
180.0
138.0
229.0
229.0
200.0
151.0
kW
21.40
21.70
22.20
22.90
22.00
22.00
22.60
23.30
22.40
22.40
22.80
23.50
115
TC
195.0
200.0
215.0
232.0
210.0
210.0
223.0
239.0
220.0
220.0
228.0
244.0
SHC
195.0
184.0
153.0
120.0
210.0
209.0
175.0
134.0
220.0
220.0
196.0
147.0
kW
23.30
23.40
24.00
24.60
23.80
23.80
24.30
25.00
24.20
24.20
24.50
25.20
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW
— Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC
— Total Capacity (1000 Btuh) Gross
5
0TF
Q0
04-
0
1
2
56
6D
/E
150
-2
40