53
ELECTRICAL DATA
566D150-240
LEGEND
*Units are suitable for use on electrical systems where voltage supplied to the
unit terminals is not below or above the listed limits.
†Fuse or HACR circuit breaker.
NOTES:
1. The MCA and MOCP values are calculated in accordance with the National
Electrical Code (NEC), Article 440.
2. Motor RLA and LRA values are established in accordance with Underwrit-
ers’ Laboratories (UL), Standard 1995.
3. The 575-v units are UL, Canada-listed only.
566E150-240
LEGEND
*Units are suitable for use on electrical systems where voltage supplied to the
unit terminals is not below or above the listed limits.
†Fuse or HACR circuit breaker.
NOTES:
1. The MCA and MOCP values are calculated in accordance with the National
Electrical Code (NEC), Article 440.
2. Motor RLA and LRA values are established in accordance with Underwrit-
ers’ Laboratories (UL), Standard 1995.
3. The 575-v units are UL, Canada-listed only.
4. Convenience outlet is available as either a factory-installed option or a field-
installed accessory and is 115-v, 1ph, 60 Hz.
UNIT
SIZE
NOMINAL
VOLTAGE
(3-Ph, 60 Hz)
VOLTAGE
RANGE*
COMPRESSOR
FAN MOTORS (Qty 2)
POWER SUPPLY
RLA
LRA
FLA (ea)
Fan No.
kW
MCA
MOCP†
ICF
Min
Max
1
2
566D
150
208/230
187
253
49.3
191
4.3
3.7
1.41
69.6
100
199
460
414
528
22.1
80
2.3
1.9
31.7
50
84
575
518
660
17.9
69
1.8
1.8
25.6
40
73
180
208/230
187
253
63.6
266
4.3
3.7
1.41
87.5
125
274
460
414
528
29.3
120
2.3
1.9
40.7
60
124
575
518
660
23.8
96
1.8
1.8
33.0
50
100
240
208/230
187
254
67.9
345
4.3
3.7
1.41
93.4
150
353
460
414
508
34.7
173
2.3
1.9
48.1
80
177
575
518
632
28.8
120
1.8
1.8
40.1
60
124
FLA
— Full Load Amps
HACR
— Heating, Air Conditioning and
Refrigeration
ICF
— Maximum Instantaneous Current Flow
During Start-Up (LRA of compressor
plus total FLA of fan motors)
kW
— Total Fan Motor Input (kilowatts)
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps per NEC,
Section 430-24
MOCP — Maximum Overcurrent Protection (amps)
RLA
— Rated Load Amps (compressor)
UNIT
SIZE
FACTORY-
INSTALLED
OPTION
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE*
COMPRESSOR 1
COMPRESSOR 2
FAN MOTORS
Qty 2)
POWER
SUPPLY
FLA (ea)
Fan No.
kW
Min
Max
RLA
LRA
RLA
LRA
1
2
MCA
MOCP†
ICF
566E
150
NONE OR DISCONNECT
CONVENIENCE OUTLET
208/230
187
253
20.7
156
20.7
156
4.3
3.7
1.41
55.6
70
186
63.5
80
194
NONE OR DISCONNECT
CONVENIENCE OUTLET
460
414
528
10.0
75
10.0
75
2.3
1.9
1.41
27.7
35
90
31.3
40
94
NONE OR DISCONNECT
CONVENIENCE OUTLET
575
518
660
8.2
54
8.2
54
1.8
1.8
1.41
23.1
30
67
25.9
30
70
180
NONE OR DISCONNECT
CONVENIENCE OUTLET
208/230
187
253
32.1
195
32.1
195
4.3
3.7
1.41
81.2
100
236
89.2
100
244
NONE OR DISCONNECT
CONVENIENCE OUTLET
460
414
528
16.4
95
16.4
95
2.3
1.9
1.41
42.1
50
117
45.7
60
120
NONE OR DISCONNECT
CONVENIENCE OUTLET
575
518
660
12.0
80
12.0
80
1.8
1.8
1.41
31.6
40
97
34.5
40
99
240
NONE OR DISCONNECT
CONVENIENCE OUTLET
208/230
187
253
37.8
239
37.8
239
4.3
3.7
1.41
94.1
125
286
102.0
150
294
NONE OR DISCONNECT
CONVENIENCE OUTLET
460
414
528
19.2
125
19.2
125
2.3
1.9
1.41
48.4
60
149
52.0
70
153
NONE OR DISCONNECT
CONVENIENCE OUTLET
575
518
660
13.8
80
13.8
80
1.8
1.8
1.41
35.7
45
98
38.5
50
101
FLA
— Full Load Amps
HACR
— Heating, Air Conditioning and
Refrigeration
ICF
— Maximum Instantaneous Current Flow
During Start-Up (LRA of compressor
plus total FLA of fan motors)
kW
— Total Fan Motor Input (kilowatts)
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps per NEC,
Section 430-24
MOCP — Maximum Overcurrent Protection (amps)
RLA
— Rated Load Amps (compressor)
5
0TF
Q0
04-
0
1
2
56
6D
/E
150
-2
40