Bryant 569F Manual De Usuario

Descargar
Página de 84
69
PERFORMANCE DATA (cont)
FAN PERFORMANCE DATA — 524A-C
WITH HIGH CAPACITY COIL — 1.4-2.4 in. wg ESP
LEGEND
Bold
indicates field-supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than
the standard motor and standard drive combination is required. Refer to
fan motor and drive tables, pages 79-81, to complete selection.
NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit size 300;
1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See table on page 70 for factory-supplied
filter pressure drop.
3. The medium-static drive and standard motor combination is not
available for 300 size. Use alternate motor if medium-static drive is
required for these sizes.
UNIT
524A-C
(High-Capacity
4-Row Coil)
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.4
1.6
1.8
2.0
2.2
2.4
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
072
1,800
921
1.07
975
1.23
1026
1.39
1074
1.55
1120
1.72
1164
1.90
2,100
942
1.26
997
1.43
1048
1.61
1097
1.79
1143
1.97
1186
2.16
2,400
963
1.47
1017
1.66
1069
1.85
1118
2.05
1164
2.25
2,700
987
1.71
1039
1.91
1090
2.12
1138
2.33
1185
2.55
3,000
1015
1.99
1065
2.20
1113
2.42
1161
2.65
090
2,250
930
1.29
986
1.47
1039
1.65
1089
1.84
1136
2.03
1181
2.22
2,600
950
1.53
1005
1.72
1057
1.92
1107
2.13
1154
2.33
3,000
980
1.86
1031
2.06
1081
2.27
1129
2.49
1175
2.72
3,400
1018
2.26
1065
2.48
1111
2.70
1156
2.93
3,750
1057
2.69
1101
2.92
1144
3.15
1186
3.39
120
3,000
961
1.78
1120
1.98
1062
2.19
1111
2.41
1158
2.64
3,500
1005
2.27
1052
2.49
1098
2.71
1142
2.94
1186
3.18
4,000
1058
2.90
1101
3.13
1143
3.36
1184
3.60
4,500
1116
3.66
1157
3.91
1196
4.16
5,000
1176
4.56
150
3,750
912
2.39
971
2.76
1300
3.14
1083
3.54
1135
3.95
1185
4.36
4,300
928
2.75
982
3.13
1036
3.53
1087
3.94
1138
4.37
1187
4.81
5,000
956
3.30
1072
3.71
1056
4.13
1104
4.56
1151
5.00
1196
5.46
5,700
990
3.96
1039
4.40
1086
4.85
1130
5.31
1174
5.78
6,250
1019
4.54
1067
5.02
1112
5.50
1156
5.99
1198
6.49
180
4,500
912
2.75
967
3.12
1019
3.52
1070
3.92
1120
4.35
1168
4.79
5,300
942
3.34
992
3.76
1041
4.18
1088
4.61
1134
5.06
1179
5.52
6,000
971
3.95
1020
4.40
1067
4.86
1112
5.33
1156
5.81
1198
6.29
6,800
1005
4.72
1054
5.23
1101
5.75
1145
6.27
1187
6.79
7,500
1036
5.48
1084
6.04
1131
6.61
1174
7.17
240
6,000
961
3.86
1011
4.31
1058
4.77
1104
5.24
1147
5.71
7,000
1000
4.79
1050
5.32
1097
5.85
1142
6.38
1184
6.91
8,000
1041
5.88
1090
6.47
1137
7.07
1181
7.67
9,000
1086
7.21
1133
7.82
1178
8.47
10,000
1138
8.83
1240
9.46
300
7,500
874
5.33
897
5.91
940
6.80
990
7.50
8,750
886
5.36
930
6.13
982
7.32
1020
8.10
10,000
930
6.60
969
7.20
1072
7.89
1045
8.71
11,250
976
8.25
1150
8.86
1051
9.49
1086
10.17
12,500
1023
10.20
1061
10.88
1097
11.56
Bhp — Brake Horsepower Input to Fan
ESP — External Static Pressure
50
TF
Q00
4
-012
52
4A0
7
2-
30