Bryant 569F Manual De Usuario

Descargar
Página de 84
70
PERFORMANCE DATA (cont)
FACTORY-SUPPLIED FILTER PRESSURE DROP
ACCESSORY PLENUM AIR THROW DATA
Throw distances shown are for 75 fpm terminal velocity. Use the follow-
ing multipliers to determine throw values for other terminal velocities.
ACCESSORY PRESSURE DROP (in. wg)
UNIT
524A-B
524A-C
AIRFLOW
(Cfm)
PRESSURE DROP
(in. wg)
072
1,800
2,400
3,000
0.05
0.08
0.11
090
2,250
3,000
3,750
0.07
0.11
0.15
120
3,000
4,000
5,000
0.11
0.17
0.23
150
3,750
5,000
6,250
0.06
0.10
0.13
180
4,500
6,000
7,500
0.08
0.12
0.17
240
6,000
8,000
10,000
0.12
0.19
0.26
300
7,500
10,000
12,500
0.15
0.22
0.30
UNIT
524A
AIRFLOW
(Cfm)
VANE DEFLECTION
Straight
21½°
45°
072
2,400
39
33
24
090
3,000
45
38
28
102
3,400
49
41
30
120
4,000
55
46
33
150
5,000
45
38
28
180
6,000
50
43
31
240
8,000
60
51
37
300
10,000
76
65
47
TERMINAL VELOCITY
(Fpm)
THROW FACTOR
50
X 1.50
100
X 0.75
150
X 0.50
UNIT
524A
AIRFLOW
(Cfm)
DISCHARGE
PLENUM
RETURN AIR
GRILLE
HEATING COILS
ECONOMIZER
Hot Water
Steam
Electric
072
1,800
2,400
3,000
0.06
0.10
0.14
0.01
0.01
0.02
0.10
0.16
0.23
0.10
0.16
0.23
0.04
0.06
0.10
0.05
0.07
0.09
090
2,250
3,000
3,750
0.09
0.14
0.21
0.01
0.02
0.03
0.15
0.23
0.35
0.15
0.23
0.35
0.06
0.10
0.15
0.06
0.09
0.15
102
2,550
3,400
4,250
0.11
0.17
0.24
0.02
0.03
0.04
0.18
0.28
0.41
0.18
0.28
0.41
0.07
0.12
0.19
0.07
0.13
0.19
120
3,000
4,000
5,000
0.14
0.22
0.32
0.02
0.04
0.06
0.23
0.37
0.53
0.23
0.37
0.53
0.10
0.17
0.26
0.09
0.17
0.28
150
3,750
5,000
6,250
0.07
0.12
0.17
0.01
0.02
0.02
0.11
0.17
0.25
0.11
0.17
0.25
0.04
0.07
0.11
0.05
0.07
0.11
180
4,500
6,000
7,500
0.10
0.16
0.23
0.01
0.02
0.03
0.15
0.23
0.33
0.15
0.23
0.33
0.06
0.10
0.15
0.06
0.09
0.15
240
6,000
8,000
10,000
0.16
0.26
0.37
0.02
0.04
0.06
0.23
0.37
0.53
0.23
0.37
0.53
0.10
0.17
0.26
0.09
0.17
0.28
300
7,500
10,000
12,500
0.15
0.24
0.34
0.02
0.03
0.05
0.28
0.44
0.63
0.28
0.44
0.63
0.09
0.16
0.24
0.06
0.09
0.14
50
TF
Q00
4
-0
12
524
A
0
72-
30