S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
65-0303—05
22
Fig. 39. R7911 Steam Configuration.
Outdoor Reset Parameters 
(R7910A Hydronic Control Only)
Table 10 displays Outdoor Reset configuration parameters. 
Pressing the left or right arrow displays Lead Lag, which lists 
the same parameters.
Fig. 40. Outdoor reset configuration.
Modulation Rate 
Sensor
Local
P-gain
Gain applied for the P portion of the 
PID equation
0-400
I-gain
Gain applied for the I portion of the 
PID equation
0-400
D-gain
Gain applied for the D portion of the 
PID equation
0-400
Hysteresis step time Time between hysteresis step 
changes: 0-600 seconds (0=Disable 
hysteresis stepping)
Table 9. Steam Configuration Parameters
Parameter
Comment
Steam enable
Disable/enable steam feature 
Steam demand 
source
Sensor and LCI
Sensor and Remote Stat
Sensor and Stat Terminal
Sensor Only
Steam pressure 
setpoint
Setpoint for normal modulation
Adjustable 0 to 15 or 0 to 150 (sensor 
dependant)
Steam time of day 
setpoint
Setpoint when TOD switch on 
Adjustable 0 to 15 or 0 to 150 (sensor 
dependant)
Minimum steam 
pressure
Establishes setpoint for the 4ma. input. 
Adjustable 0 to 15 or 0 to 150 (sensor 
dependant)
Steam pressure off 
hysteresis
Differential below setpoint when boiler 
is turned off
Adjustable 0 to 15 or 0 to 150 (sensor 
dependant)
Table 8. Central Heat Hydronic 
Configuration Parameters. (Continued)
Parameter
Comment
Steam pressure on 
hysteresis
Differential from setpoint when boiler
is turned on.
Adjustable 0 to 15 or 0 to 150 (sensor 
dependant)
Steam hysteresis 
step time
Time between hysteresis changes 0 to 
600 seconds (0=disable)
Steam P Gain
Gain applied for the P portion of the
PID equation
0-400
Steam I Gain
Gain applied for the I portion of the PID 
Equation - 0-400
Steam D Gain
Gain applied for the D portion of the
PID equation
0-400
Steam 4-20 ma 
remote control
uses 4-20ma remote control function to 
control either the setpoint or 
modulation for Steam 
Disable, setpoint, modulation
Table 10. Outdoor Reset Configuration Parameters.
Parameter
Comment
Maximum outdoor 
temperature
-40 °F to 266 °F (-40 °C to 130 °C)
Minimum outdoor 
temperature
-40 °F to 266 °F (-40 °C to 130 °C)
Low water 
temperature
-40 °F to 266 °F (-40 °C to 130 °C)
Minimum water 
temperature
-40 °F to 266 °F (-40 °C to 130 °C)
Maximum off point
-40 °F to 266 °F (-40 °C to 130 °C)
Table 9. Steam Configuration Parameters